SWITCHGEAR (TRIP UNIT RETROFIT KITS)<br />

Digitrip RMS Retrofit Kits for Westinghouse<br />

DS Breakers<br />

INTRODUCTION AND DESCRIPTION<br />

DS Breaker Retrofitted with<br />

Digitrip RMS 810 Retrofit Kit<br />

REPLACEMENT AND UPGRADE<br />

Create the Digitrip RMS Retrofit Kit catalog<br />

number to match the Cutler-Hammer or<br />

Westinghouse DS breaker type, retrofit kit<br />

type, protection function, rating plug type,<br />

current sensor type, CPT, and type of kit<br />

required for application. See the example<br />

provided on page 259.<br />

Application Notes for Cutler-Hammer or<br />

Westinghouse DS and DSL Power Circuit<br />

Breakers<br />

1. Retrofit kits are for use on 50 and<br />

60 Hz distribution systems.<br />

2. All retrofit kits are designed for Drawout<br />

Power Circuit Breakers only. Refer<br />

all fixed mounted breaker applications<br />

to the Cutler-Hammer Digitrip Retrofit<br />

Kit Technical Service Center at<br />

1-800-937-5487.<br />

Typical Digitrip RMS 810 Retrofit Kit<br />

for a DS Power Circuit Breaker<br />

3. The breaker compartment doors on<br />

the switchgear assembly must be free<br />

of panel mounted instruments and<br />

devices (i.e. ammeters, switches, etc.)<br />

or the retrofitted breaker may interfere<br />

with these devices when the compartment<br />

door is closed.<br />

4. When the Ground Fault (G) option is<br />

selected, please observe the following:<br />

a. For 3-phase, 3-wire solidly grounded<br />

systems, choose quantity three current<br />

sensors in the catalog number<br />

development.<br />

b. For 3-phase, 4-wire solidly grounded<br />

systems, choose quantity four current<br />

sensors in the catalog number<br />

development. Three sensors are<br />

mounted on the breaker and one<br />

sensor is mounted on the switchgear<br />

neutral. Hardware to mount<br />

Digitrip RMS Retrofit Kits for Westinghouse<br />

DS and DSL Power Circuit Breakers were<br />

first introduced in 1987. For a complete<br />

description of the Digitrip RMS Trip System<br />

and the features of Models RMS 510, 610,<br />

810, and 910, see page 247.<br />

Ratings<br />

Digitrip RMS Retrofit Kits are applied on<br />

DS <strong>breakers</strong> with frame ratings from 800A<br />

(DS-206) to 4000A (DS-840) as identified<br />

below. The rating plug and the current<br />

sensor rating act in concert to provide for<br />

a wide spectrum of overload and short<br />

<strong>circuit</strong> settings.<br />

Chronology<br />

Digitrip RMS Retrofit Kits and replacement<br />

trip units for DS Breakers became available<br />

around 1987. The Digitrip RMS 510<br />

Model is the modern day replacement for<br />

the Amptector Trip Systems.<br />

the current sensor on the switchgear<br />

neutral and provisions to wire<br />

it into the trip unit <strong>circuit</strong> (including<br />

a required pair of breaker secondary<br />

disconnecting contacts) are not<br />

included in the kit.<br />

5. RMS 510, 610, 810, and 910 Retrofit<br />

kits include a cell terminal block<br />

assembly that must be installed in the<br />

switchgear assembly. Internal switchgear<br />

wiring to accommodate the customer<br />

application schemes must be<br />

added in the field.<br />

6. RMS 610, 810, and 910 Retrofit Kits<br />

require a customer supplied 120 Vac<br />

source connected to the cell terminal<br />

block assembly to power the Digitrip<br />

RMS Digital Displays and Communications<br />

functions (as applicable).<br />