SWITCHGEAR (LOW VOLTAGE)<br />

DB Assemblies, Power Circuit Breakers<br />

and Renewal Parts<br />

PRODUCT DESCRIPTION<br />

DB Switchgear with DB Air Circuit Breakers<br />

REPLACEMENT CAPABILITIES<br />

Remanufactured DB-25 Breaker<br />

Including Digitrip RMS 810 Trip Unit<br />

March 2001<br />

Low Resolution Photo<br />

Westinghouse DB switchgear used the DB<br />

breaker in its design. Among the <strong>breakers</strong><br />

used were the DB15, DB25, DB50, DB75,<br />

DB100 and the current limiting type DBL25<br />

and DBL50. A characteristic of the DB<br />

switchgear was that the panel door could<br />

be kept closed when the breaker was in<br />

the open, test and disconnected position<br />

of the three-position DB breaker. The single<br />

position DB breaker also had this feature<br />

but did not have a test position. In<br />

either <strong>case</strong>, both the three- and single-position<br />

DB <strong>breakers</strong> utilized the electromechanical<br />

trip unit.<br />

The DB switchgear structures were<br />

approximately 90 3/8-inch high construction<br />

with a universal frame that accommodated<br />

Cutler-Hammer offers an extensive amount<br />

of products to support DB Switchgear:<br />

New DB Air Circuit Breakers<br />

Completely new factory manufactured<br />

<strong>breakers</strong> are still available for DB25, DB50,<br />

DBL25, DBL50, DBF6 and DBF16.<br />

Remanufactured DB Breakers and Factory<br />

Repair Service<br />

Factory remanufacturing of most frame<br />

sizes of DB <strong>circuit</strong> <strong>breakers</strong> are available.<br />

All are asbestos-free, in accordance with<br />

ANSI C37.59, calibrated per original specifications<br />

and equipped with Digitrip RMS<br />

510 trip units as standard.<br />

235<br />

breaker compartment widths of 18, 26, 30<br />

and 36 inches All main bus joints and tap<br />

connections are silver plated and tightly<br />

clamped with through-bolts to insure<br />

maximum conductivity. The outdoor<br />

switchgear was a walk-in type with<br />

rear hinged doors for easy access to<br />

connections.<br />

Ratings<br />

DB Switchgear Bus 800 – 4000A<br />

DB Breaker 15 – 4000A<br />

Voltage 208 – 600V<br />

Interrupting Capacity 15 – 150kA<br />

Chronology<br />

This switchgear started in East Pittsburgh,<br />

PA approximately 1950 and final production<br />

ended around 1980.<br />

DB Breaker Parts<br />

A complete line of DB breaker replacement<br />

parts are available built from the original<br />

drawings and design specifications. Among<br />

the items stocked are asbestos-free arc<br />

chutes, complete pole units, contacts,<br />

primary disconnects and coils.<br />

DB Switchgear Structure Parts<br />

DB switchgear parts are available for most<br />

DB designs. Newly manufactured replacement<br />

parts (such as doors, breaker provisions,<br />

lift trucks, metering, etc.) are<br />

available.<br />

Digitrip Trip Unit Retrofit Kits<br />

Trip unit retrofit kits are available for all<br />

DB breaker frames. Refer to pages 256-<br />

257 of this publication.<br />