molded case circuit breakers - Eaton Canada
molded case circuit breakers - Eaton Canada
molded case circuit breakers - Eaton Canada
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
SWITCHGEAR (LOW VOLTAGE)<br />
DB Assemblies, Power Circuit Breakers<br />
and Renewal Parts<br />
PRODUCT DESCRIPTION<br />
DB Switchgear with DB Air Circuit Breakers<br />
REPLACEMENT CAPABILITIES<br />
Remanufactured DB-25 Breaker<br />
Including Digitrip RMS 810 Trip Unit<br />
March 2001<br />
Low Resolution Photo<br />
Westinghouse DB switchgear used the DB<br />
breaker in its design. Among the <strong>breakers</strong><br />
used were the DB15, DB25, DB50, DB75,<br />
DB100 and the current limiting type DBL25<br />
and DBL50. A characteristic of the DB<br />
switchgear was that the panel door could<br />
be kept closed when the breaker was in<br />
the open, test and disconnected position<br />
of the three-position DB breaker. The single<br />
position DB breaker also had this feature<br />
but did not have a test position. In<br />
either <strong>case</strong>, both the three- and single-position<br />
DB <strong>breakers</strong> utilized the electromechanical<br />
trip unit.<br />
The DB switchgear structures were<br />
approximately 90 3/8-inch high construction<br />
with a universal frame that accommodated<br />
Cutler-Hammer offers an extensive amount<br />
of products to support DB Switchgear:<br />
New DB Air Circuit Breakers<br />
Completely new factory manufactured<br />
<strong>breakers</strong> are still available for DB25, DB50,<br />
DBL25, DBL50, DBF6 and DBF16.<br />
Remanufactured DB Breakers and Factory<br />
Repair Service<br />
Factory remanufacturing of most frame<br />
sizes of DB <strong>circuit</strong> <strong>breakers</strong> are available.<br />
All are asbestos-free, in accordance with<br />
ANSI C37.59, calibrated per original specifications<br />
and equipped with Digitrip RMS<br />
510 trip units as standard.<br />
235<br />
breaker compartment widths of 18, 26, 30<br />
and 36 inches All main bus joints and tap<br />
connections are silver plated and tightly<br />
clamped with through-bolts to insure<br />
maximum conductivity. The outdoor<br />
switchgear was a walk-in type with<br />
rear hinged doors for easy access to<br />
connections.<br />
Ratings<br />
DB Switchgear Bus 800 – 4000A<br />
DB Breaker 15 – 4000A<br />
Voltage 208 – 600V<br />
Interrupting Capacity 15 – 150kA<br />
Chronology<br />
This switchgear started in East Pittsburgh,<br />
PA approximately 1950 and final production<br />
ended around 1980.<br />
DB Breaker Parts<br />
A complete line of DB breaker replacement<br />
parts are available built from the original<br />
drawings and design specifications. Among<br />
the items stocked are asbestos-free arc<br />
chutes, complete pole units, contacts,<br />
primary disconnects and coils.<br />
DB Switchgear Structure Parts<br />
DB switchgear parts are available for most<br />
DB designs. Newly manufactured replacement<br />
parts (such as doors, breaker provisions,<br />
lift trucks, metering, etc.) are<br />
available.<br />
Digitrip Trip Unit Retrofit Kits<br />
Trip unit retrofit kits are available for all<br />
DB breaker frames. Refer to pages 256-<br />
257 of this publication.<br />
R