• Specifying the initial value for the UP/DOWN control<br />

Specify the initial value to start the UP/DOWN control.<br />

Data for H61<br />

0<br />

1<br />

Initial value to start the UP/DOWN control<br />

Mode fixing the value at "0":<br />

The inverter automatically clears the value to "0" when restarted (including powered<br />

ON). Speed up by the UP command.<br />

Mode holding the final output frequency in the previous UP/DOWN control:<br />

The inverter internally holds the last output frequency set by the UP/DOWN control and<br />

applies the held frequency at the next restart (including powering ON).<br />

At the time of restart, if an UP or DOWN terminal command is entered before the internal frequency<br />

reaches the output frequency saved in the memory, the inverter saves the current output frequency into the<br />

memory and starts the UP/DOWN control with the new frequency.<br />

Pressing one of these keys overwrites the frequency held in the inverter.<br />

Initial frequency for the UP/DOWN control when the frequency command source is switched<br />

When the frequency command source is switched to the UP/DOWN control from other sources, the initial<br />

frequency for the UP/DOWN control is as listed below:<br />

Frequency command<br />

source<br />

Other than UP/DOWN<br />

(F01, C30)<br />

PID control<br />

Multi-frequency<br />

Communications link<br />

Switching command<br />

Select frequency<br />

command 2/1 (Hz2/Hz1)<br />

Cancel PID control<br />

(Hz/PID)<br />

Select multi-frequency<br />

(SS1, SS2, SS4 and SS8)<br />

Enable communications<br />

link<br />

via RS-485 or fieldbus (LE)<br />

Initial frequency for UP/DOWN control<br />

H61 = 0 H61 = 1<br />

Reference frequency given by the frequency<br />

command source used just before switching<br />

Reference frequency given by PID control (PID<br />

controller output)<br />

Reference frequency<br />

given by the<br />

frequency command<br />

source used just<br />

before switching<br />

Reference frequency<br />

at the time of previous<br />

UP/DOWN control<br />

4-31