Terminals common to all inverters<br />

Auxiliary control power input terminals [R0] and [T0]<br />

Auxiliary fan power input terminals [R1] and [T1]<br />

Recommended wire size<br />

AWG (mm 2 )<br />

14 (2.1)<br />

2 HP or above<br />

Remarks<br />

230 V series with 60 HP or above<br />

460 V series with 125 HP or above<br />

(2) Arrangement of control circuit terminals (common to all inverter types)<br />

Terminal type Screw size: M3 (0.7 N·m) Spring (screwless)<br />

Recommended wiring size<br />

0.65 to 0.82 (AWG 19 or<br />

(mm 2 0.75<br />

)*<br />

18)<br />

* Using wires exceeding the recommended sizes may lift the front cover<br />

depending upon the number of wires used, impeding keypad's normal<br />

operation.<br />

2.3.3 Wiring precautions<br />

Follow the rules below when performing wiring for the inverter.<br />

(1) Make sure that the source voltage is within the rated voltage range specified on the nameplate.<br />

(2) Be sure to connect the three-phase power wires to the main circuit power input terminals L1/R, L2/S and L3/T of<br />

the inverter. If the power wires are connected to other terminals, the inverter will be damaged when the power is<br />

turned ON.<br />

(3) Always connect the grounding terminal to prevent electric shock, fire or other disasters and to reduce electric<br />

noise.<br />

(4) Use crimp terminals covered with insulated sleeves for the main circuit terminal wiring to ensure a reliable<br />

connection.<br />

(5) Keep the power supply wiring (primary circuit) and motor wiring (secondary circuit) of the main circuit, and control<br />

circuit wiring as far away as possible from each other.<br />

(6) After removing a screw from the main circuit terminal block, be sure to restore the screw even if no wire is<br />

connected.<br />

(7) Use the wiring guide to separate wiring. For inverters of 5 HP or below, the wiring guide separates the main circuit<br />

wires and the control circuit wires. For those of 7.5 to 40 HP, it separates the upper and lower main circuit wires,<br />

and control circuit wires. Be careful about the wiring order.<br />

e.g. <strong>EQ7</strong>-4005-C<br />

e.g. <strong>EQ7</strong>-2020-C<br />

• Preparing for the wiring guide<br />

Inverters of 20 to 40 HP (three-phase, 230 V series) are sometimes lacking in wiring space for main circuit wires<br />

depending upon the wire materials used. To assure a sufficient wiring space, remove the clip-off sections (see<br />

below) as required with a nipper. Note that the enclosure rating of IP20 may not be ensured when the wiring guide<br />

itself is removed to secure a space for thick main circuit wiring.<br />

2-8