The table below shows the conditions for zero speed control to be enabled or disabled.<br />

At startup<br />

At stop<br />

Speed command Run command Data for d24 Operation<br />

OFF ― Stop (Gate OFF)<br />

Below the starting and<br />

0 Stop (Gate OFF)<br />

stop frequencies<br />

ON<br />

1 Zero speed control<br />

Below the stop<br />

ON ― Zero speed control<br />

frequency<br />

OFF ― Stop (Gate OFF)<br />

• Stop Frequency (Detection mode) (F38) (Under vector control with speed sensor)<br />

F38 specifies whether to use the detected or reference speed as criterion to shut down the inverter output. Usually<br />

the inverter uses the detected speed. However, if the inverter undergoes a load exceeding its capability, e.g., an<br />

external excessive load, the motor cannot stop so that the detected speed may not reach the stop frequency level.<br />

When such a situation arises, select an appropriate speed that can reach the stop frequency level even if the<br />

detected speed does not, in order to stop the inverter without fail for general fail-safe operation.<br />

- Data setting range: 0 (Detected speed)<br />

1 (Reference speed)<br />

4-53