• Torque limiter levels specified via communications link (S10, S11)<br />

The torque limiter levels can be changed via the communications link. Function codes S10 and S11 exclusively<br />

reserved for the communications link respond to function codes F40 and F41.<br />

• Switching torque limiters<br />

The torque limiters can be switched by the function code setting and the terminal command TL2/TL1 ("Select<br />

torque limiter level 2/1") assigned to any of the digital input terminals.<br />

To assign the TL2/TL1 as the terminal function, set any of E01 through E07 to "14." If no TL2/TL1 is assigned,<br />

torque limiter levels 1-1 and 1-2 (F40 and F41) take effect by default.<br />

• Torque limiter (Operating conditions) (H73)<br />

H73 specifies whether the torque limiter is enabled or disabled during acceleration/deceleration and running at<br />

constant speed.<br />

Data for H73 During accelerating/decelerating During running at constant speed<br />

0 Enable Enable<br />

1 Disable Enable<br />

2 Enable Disable<br />

• Torque limiter (Frequency increment limit for braking) (H76)<br />

Data setting range: 0.0 to 500.0 (Hz)<br />

H76 specifies the increment limit of the frequency in limiting torque for braking. The factory default is 5.0 Hz. If the<br />

increasing frequency during braking reaches the limit value, the torque limiters no longer function, resulting in an<br />

overvoltage trip. Such a problem may be avoided by increasing the setting value of H76.<br />

The torque limiter and current limiter are very similar in function. If both are activated concurrently, they<br />

may conflict with each other and cause hunting (undesirable oscillation of the system). Avoid concurrent<br />

activation of these limiters.<br />