3.4.3 Checking changed function codes -- Menu #2 "Data Checking" --<br />

Menu #2 "Data Checking" in Programming mode allows you to check function codes and their data that has been<br />

changed. The function codes whose data has been changed from the factory defaults are marked with an asterisk ( ).<br />

Select a function code and press the key to view or change its data.<br />

The LCD screen transition from Menu #2 is the same as that from Menu #1 "Data Setting," except a list of function codes<br />

as shown below.<br />

Function code<br />

Changed<br />

Function code data<br />

Operation guide, scrolling horizontally to display the function of each key.<br />

Basic key operation<br />

Figure 3.11 List of Function Codes<br />

Same as the basic key operation for Menu #1 "Data Setting."<br />

3.4.4 Monitoring the running status -- Menu #3 "Drive Monitoring" --<br />

Menu #3 "Drive Monitoring" in Programming mode allows you to monitor the running status during maintenance and test<br />

running.<br />

Table 3.7 Drive Monitoring Items<br />

Page # in<br />

operation<br />

guide<br />

1<br />

2<br />

3<br />

Item Symbol Description<br />

Output frequency Fot1 Output frequency (before slip compensation)<br />

Output frequency Fot2 Output frequency (after slip compensation)<br />

Output current Iout Output current<br />

Output voltage Vout Output voltage<br />

Calculated torque TRQ Calculated output torque generated by motor<br />

Reference frequency Fref Frequency specified by a frequency command<br />

Running direction<br />

FWD<br />

REV<br />

(Blank)<br />

Forward<br />

Reverse<br />

Stopped<br />

Current limit IL Current limiting<br />

Undervoltage<br />

Voltage limit<br />

LU<br />

VL<br />

Undervoltage detected<br />

Voltage limiting<br />

Torque limit TL Torque limiting<br />

Speed limit SL Speed limiting<br />

<strong>Motor</strong> selected M1-M4 <strong>Motor</strong> 1 to 4<br />

Drive control<br />

<strong>Motor</strong> speed<br />

VF<br />

DTV<br />

VF-SC<br />

VF-PG<br />

VC-SL<br />

VC-PG<br />

SYN<br />

V/f control without slip compensation<br />

Dynamic torque vector control<br />

V/f control with slip compensation<br />

Dynamic torque vector control with speed sensor<br />

Vector control without speed sensor<br />

Vector control with speed sensor<br />

(Output frequency Hz)<br />

×<br />

120<br />

P01<br />

Load shaft speed LOD Output frequency (Hz) Function code E50<br />

Line speed LIN Output frequency (Hz) Function code E50<br />

Constant peripheral<br />

speed control monitor<br />

LSC<br />

Actual peripheral speed under constant peripheral speed<br />

control<br />

3-12