Configuring a reference frequency<br />
[ 1 ] Using and keys (F01 = 0 (factory default) or 8)<br />
(1) Set function code F01 at "0" or "8" ( / keys on keypad). This cannot be done when the keypad is in<br />
Programming or Alarm mode. To enable frequency setting using the and keys, first place the keypad in<br />
Running mode.<br />
(2) Press the or key. The 7-segment LED monitor displays the reference frequency and the LCD monitor<br />
displays the related information including the operation guide, as shown below.<br />
The lowest digit blinks.<br />
Keypad takes precedence.<br />
Allowable entry range<br />
Operation guide<br />
Example of Reference Frequency Configuration Screen<br />
(3) To change the reference frequency, press the or key again. To save the new setting into the<br />
inverter's memory, press the key (when E64 = 1 (factory default)). When the power is turned ON next time,<br />
the new setting will be used as an initial reference frequency.<br />
In addition to saving with the key described above, "Automatic saving when the main power is turned<br />
OFF" is also possible (when E64 = 0).<br />
When you start accessing the reference frequency or any other parameter with the and keys,<br />
the least significant digit on the display blinks and starts changing. As you are holding down the key,<br />
blinking gradually moves to the upper digit places and the upper digits becomes changeable.<br />
Pressing the<br />
digits.<br />
key moves the changeable digit place (blinking), making it easy to change upper<br />
Setting function code C30 at "0" (Enable / keys on the keypad) and selecting frequency<br />
command 2 as a frequency command source makes it possible to access the reference frequency in<br />
the same manner using the and keys.<br />
If you have set function code F01 at "0" ( / keys on keypad) but have selected a frequency<br />
command source other than frequency 1 (i.e., frequency 2, via communications link, or as a<br />
multi-frequency), then using the or key cannot change the frequency command even if the<br />
keypad is in Running mode. Pressing either of these keys just displays the currently selected<br />
frequency command.<br />
Setting function code F01 at "8" ( / keys on keypad) enables the balanceless-bumpless<br />
switching. When the frequency command source is switched to the keypad from any other source, the<br />
inverter inherits the current frequency that has applied before switching, providing smooth switching<br />
and shockless running.<br />
When the frequency command source is other than the digital reference setting, the LCD monitor<br />
displays the following.<br />
Keypad is not enabled.<br />
Setting on the analog terminal [12] is<br />
effective. (See the table below.)<br />
4-27