• Running forward -- FRUN (Function code data = 52)<br />

Running reverse -- RRUN (Function code data = 53)<br />

Output signal Assigned data Running forward Running reverse Inverter stopped<br />

FRUN 52 ON OFF OFF<br />

RRUN 53 OFF ON OFF<br />

• In remote operation -- RMT (Function code data = 54)<br />

This output signal comes ON when the inverter switches from local to remote mode.<br />

For details of switching between remote and local modes, refer to user <strong>Manual</strong> Chapter 4, Section 4.2.2<br />

"Remote and local modes."<br />

• Terminal [C1] wire break -- C1OFF (Function code data = 59)<br />

This output signal comes ON when the inverter detects that the input current to terminal [C1] drops below 2 mA<br />

interpreting it as the terminal [C1] wire broken.<br />

• Speed valid -- DNZS (Function code data = 70)<br />

This output signal comes ON when the reference or detected speed exceeds the stop frequency specified by<br />

function code F25. It goes OFF when the speed is below the stop frequency for 100 ms or longer.<br />

Under vector control with speed sensor, F38 switches the decision criterion between the reference and detected<br />

speed. Under vector control without speed sensor, the reference speed is used as a decision criterion. ( Refer<br />

to the descriptions of F25 and F38.)<br />

• Alarm output (for any alarm) -- ALM (Function code data = 99)<br />

This output signal comes ON if any of the protective functions is activated and the inverter enters Alarm mode.<br />

• Enable circuit failure detected -- DECF (Function code data = 101)<br />

This output signal comes ON when the inverter detects a failure of the Enable circuit(*1).<br />

Configure a feedback circuit of the Enable input function as needed to feed back the transistor output of the<br />

DECF-assigned inverter to the reset input of the upper safety relay unit for turning the Enable command off and<br />

shutdown of the inverter output.<br />

4-92