Table 2.8 lists function of each slide switch.<br />

Switch<br />

SW1<br />

SW2<br />

SW3<br />

Table 2.8 Function of Each Slide Switch<br />

Function<br />

Switches the service mode of the digital input terminals between SINK and SOURCE.<br />

▪ This switches the input mode of digital input terminals [X1] to [X7], [FWD] and [REV] to be<br />

used as the SINK or SOURCE mode.<br />

▪ The factory default is SINK.<br />

Switches the terminating resistor of RS-485 communications port on the inverter ON and OFF.<br />

(RS-485 communications port 2, on the control PCB)<br />

▪ If the inverter is connected to the RS-485 communications network as a terminating device,<br />

turn SW2 to ON.<br />

Switches the terminating resistor of RS-485 communications port on the inverter ON and OFF.<br />

(RS-485 communications port 1, for connecting the keypad)<br />

▪ To connect a keypad to the inverter, turn SW3 to OFF. (Factory default)<br />

▪ If the inverter is connected to the RS-485 communications network as a terminating device,<br />

turn SW3 to ON.<br />

Switches the output form of analog output terminals [FM1] and [FM2] between voltage and<br />

current.<br />

When changing the setting of SW4 and SW6, also change the data of function codes F29 and<br />

F32, respectively.<br />

SW4/SW6<br />

[FM1]<br />

[FM2]<br />

Output form<br />

SW4 F29 data SW6 F32 data<br />

Voltage output (Factory default) VO1 0 VO2 0<br />

Current output IO1 1 IO2 1<br />

Switches the property of the analog input terminal [C1] between analog setting current input,<br />

PTC thermistor input, and NTC thermistor input.<br />

When changing this switch setting, also change the data of function code H26.<br />

SW5<br />

Function SW5 H26 data<br />

Analog setting current input (Factory default) C1 0<br />

PTC thermistor input PTC/NTC 1 (alarm) or 2<br />

(warning)<br />

NTC thermistor input PTC/NTC 3<br />

Figure 2.20 shows the location of slide switches on the control PCB for the input/output terminal configuration.<br />

Switch Configuration and Factory Defaults<br />

Factory<br />

default<br />

SW1 SW2 SW3<br />

SINK<br />

SOURCE<br />

SW4/SW<br />

6<br />

SW5<br />

OFF OFF VO1/VO2 C1<br />

ON<br />

---<br />

ON<br />

IO1/IO2<br />

PTC/NTC<br />

Figure 2.20 Location of the Slide Switches<br />

on the Control PCB<br />

To move a switch slider, use a tool with a narrow tip (e.g., a tip of tweezers). Be careful not to touch other<br />

electronic parts, etc. If the slider is in an ambiguous position, the circuit is unclear whether it is turned ON<br />

or OFF and the digital input remains in an undefined state. Be sure to place the slider so that it contacts<br />

either side of the switch.<br />