2.5 Input Power and <strong>Motor</strong> Connection<br />

Checking prior to powering on<br />

Fig.2.23 below shows the electrical connections for the input power and motor terminals for various <strong>EQ7</strong> DRIVE<br />

models. Verify the input power and motor terminals of the model you are installing. WITH POWER OFF, make the<br />

appropriate connections.<br />

Make sure to follow good wiring practices and all applicable codes. Ensure that the equipment is grounded<br />

properly as shown.<br />

DANGER, LETHAL VOLTAGES ARE PRESENT- Before applying power to the <strong>EQ7</strong> drive, ensure that the<br />

terminal cover is fastened and all wiring connections are secure. After the power has been turned OFF, wait at<br />

least ten minutes until the charge indicator extinguishes completely before touching any wiring, circuit boards<br />

or components.<br />

WARNING DO NOT CONNECT ANY OF THE<br />

FOLLOWING TERMINALS TO EARTH GROUND<br />

DB<br />

P1 P(+) N(-)<br />

INPUT POWER<br />

*1 *1<br />

MOTOR<br />

GND<br />

L1/R L2/S L3/T<br />

<strong>EQ7</strong><br />

U V W<br />

GND<br />

Ground<br />

(R/L1)<br />

(S/L2)<br />

(T/L3)<br />

To change direction of<br />

motor rotation swap any<br />

two of the three motor<br />

leads.<br />

Input<br />

Protection<br />

(Fuse or Magnetic<br />

Contactor)<br />

(U/T1)<br />

(V/T2)<br />

(W/T3)<br />

Ground<br />

P1<br />

P(+)<br />

L1 L2 L3<br />

Use L1, L2, L3 for<br />

3Ø Input Power<br />

Use L1 & L3 for<br />

2<br />

1Ø Input Power *<br />

3Ø Induction<br />

motor<br />

Connect<br />

frame to<br />

ground<br />

Fig. 2.23<br />

DCR<br />

*1. Refer to page 2-11 & 2-12 for connecting a DC reactor from the terminals P1 and P(+).<br />

*2. Make sure the drive is properly sized for single phase input (consult factory).<br />

(Refer to Table 2.6 Recommended Wire Sizes in this manual).<br />

2-28