22.11.2014 Views

EQ7 Series Instruction Manual - TECO-Westinghouse Motor Company

EQ7 Series Instruction Manual - TECO-Westinghouse Motor Company

EQ7 Series Instruction Manual - TECO-Westinghouse Motor Company

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Chapter 9 Using PID Control for Constant Flow / Pressure Applications<br />

9.1 What is PID Control?<br />

The PID function in the <strong>EQ7</strong> drive can be used to maintain a constant process variable such as pressure, flow,<br />

temperature by regulating the output frequency (motor speed). A feedback device (transducer) signal is used to<br />

compare the actual process variable to a specified setpoint. The difference between the set-point and feedback<br />

signal is called the error signal.<br />

The PID control tries to minimize this error to maintain a constant process variable by regulating the output frequency<br />

(motor speed).<br />

PID Control<br />

Cancellation<br />

(E01 – E07 = 20)<br />

F01 Frequency<br />

Command 1<br />

PID Command<br />

Selected by<br />

J02 (0 Default)<br />

0: Keypad (Default)<br />

*<br />

Terminals:<br />

1: 12- 0-10VDC<br />

1: V2 – 0-10VDC<br />

1: C1 – 0-20mA<br />

3: Up/Down<br />

4: Communication<br />

+<br />

-<br />

Proportional Gain<br />

(0.000 - 30.000)<br />

J03<br />

Integral Time<br />

(0.1 - 3600.0 Sec.)<br />

J04<br />

Derivative Time<br />

(0.00 - 600.00 Sec.)<br />

J05<br />

+<br />

+<br />

+<br />

PID OFF<br />

Normal<br />

Operation<br />

Inverse<br />

Operation<br />

Dancer<br />

Control<br />

J01 PID Control<br />

OFF<br />

ON<br />

*Terminal<br />

12<br />

Feedback Filter<br />

(0.0 - 900.0 Sec.)<br />

PID Control Block Diagram<br />

0<br />

1<br />

2<br />

3<br />

J06<br />

Normal<br />

Operation<br />

Frequency<br />

Command<br />

Terminal 12<br />

E61 = 5<br />

Drive<br />

Section<br />

PID Feedback Signal<br />

Terminal C1<br />

E62 = 5<br />

Terminal V2<br />

E63 = 5<br />

Feedback<br />

Transducer<br />

E61, E62 or E63 = 5<br />

Feedback Signal Select<br />

* The setpoint and feedback sources<br />

cannot be the same terminals.<br />

Control<br />

Target<br />

*<br />

The amplitude of the error can be adjusted with the Proportional Gain parameter J03 and is directly related to the<br />

output of the PID controller, so the larger gain the larger the output correction.<br />

Example 1: Example 2:<br />

Gain = 1.0 Gain = 2.0<br />

Set-Point = 80% Set-Point = 80%<br />

Feedback = 78% Feedback = 78%<br />

Error = Set-point - Feedback = 2% Error = Set-point - Feedback = 2%<br />

Control Error = Gain x Error = 2% Control Error = Gain x Error = 4%<br />

Please note that an excessive gain can make the system unstable and oscillation may occur.<br />

The response time of the system can be adjusted with the Integral Gain set by parameter J04. Increasing the Integral<br />

Time will make the system less responsive and decreasing the Integral Gain Time will increase response but may<br />

result in instability of the total system.<br />

Slowing the system down too much may be unsatisfactory for the process. The end result is that these two<br />

parameters in conjunction with the acceleration (F07) and deceleration (F08) times (see chapter 8.2) are adjusted to<br />

achieve optimum performance for a particular application.<br />

For typical fan and pump applications a Proportional Gain (J03) of 2.0 and an Integral Time (J04) of 5.0 sec is<br />

recommended.<br />

9-1

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!