F03 Maximum Frequency 1<br />

F03 specifies the maximum frequency to limit the output frequency. Specifying the maximum frequency exceeding<br />

the rating of the equipment driven by the inverter may cause damage or a dangerous situation. Make sure that the<br />

maximum frequency setting matches the equipment rating.<br />

- Data setting range: 25.0 to 500.0 (Hz)<br />

• For variable torque mode inverters, set the maximum frequency at 120 Hz or below.<br />

• Under vector control with speed sensor, set the maximum frequency at 200 Hz or below, and under<br />

vector control without speed sensor, at 120 Hz or below.<br />

• If a setting exceeding the maximum setting value (e.g., 500 Hz) is made, the reference speed and<br />

analog output (FMA) will be based on the full scale/reference value (10V/500 Hz). However, the<br />

frequency is internally limited. Even if 10 V is inputted, the frequency 500 Hz will be internally limited to<br />

200 Hz.<br />

The inverter can easily accept high-speed operation. When changing the speed setting, carefully check the<br />

specifications of motors or equipment beforehand.<br />

Otherwise injuries could occur.<br />

Modifying F03 data to allow a higher reference frequency requires also changing F15 data specifying a<br />

frequency limiter (high).<br />

F04 to F05<br />

F06<br />

Base Frequency 1, Rated Voltage at Base Frequency 1<br />

Maximum Output Voltage 1<br />

H50, H51 (Non-linear V/f Pattern 1 (Frequency and Voltage))<br />

H52, H53 (Non-linear V/f Pattern 2 (Frequency and Voltage))<br />

H65, H66 (Non-linear V/f Pattern 3 (Frequency and Voltage))<br />

These function codes specify the base frequency and corresponding voltage at the base frequency essentially<br />

required for running the motor properly. If combined with the related function codes H50 through H53, H65 and<br />

H66, these function codes may customize the non-linear V/f pattern by specifying increase or decrease in voltage<br />

at any point on the V/f pattern.<br />

The following description includes setups required for the non-linear V/f pattern.<br />

At high frequencies, the motor impedance may increase, resulting in an insufficient output voltage and a decrease<br />

in output torque. To prevent this problem use F06 (Maximum Output Voltage 1) to increase the voltage. Note,<br />

however, that the inverter cannot output voltage exceeding its input power voltage.<br />

V/f point<br />

Function code<br />

Frequency Voltage<br />

Remarks<br />

The setting of the maximum output voltage is<br />

Maximum frequency F03 F06<br />

disabled when the auto torque boost, torque vector<br />

control, vector control without speed sensor, or<br />

vector control with speed sensor is selected.<br />

Base frequency F04 F05<br />

Non-linear V/f pattern 3 H65 H66 Disabled when the auto torque boost, torque vector<br />

Non-linear V/f pattern 2 H52 H53 control, vector control without speed sensor, or<br />

Non-linear V/f pattern 1 H50 H51 vector control with speed sensor is selected.<br />

4-35