• Starting frequency 1 (Holding time) (F24) Data setting range: 0.00 to 10.00 (s)<br />

F24 specifies the holding time for the starting frequency 1.<br />

• Stop frequency (F25)<br />

Data setting range: 0.0 to 60.0 (Hz)<br />

F25 specifies the stop frequency at the stop of the inverter. Under V/f control, even if the stop frequency is set at<br />

0.0 Hz, the inverter stops at 0.1 Hz.<br />

• Stop frequency (Holding time) (F39) Data setting range: 0.00 to 10.00 (s)<br />

F39 specifies the holding time for the stop frequency.<br />

If the starting frequency is lower than the stop frequency, the inverter will not output any power as long as<br />

the reference frequency does not exceed the stop frequency.<br />

Under vector control with/without speed sensor (F42 = 5, 6)<br />

At the startup, the inverter first starts at the "0" speed and accelerates to the starting frequency according to the<br />

specified acceleration time. After holding the starting frequency for the specified period, the inverter again<br />

accelerates to the reference speed according to the specified acceleration time.<br />

The inverter stops its output when the reference speed or detected one (specified by F38) reaches the stop<br />

frequency specified by F25.<br />

Specifying the holding time for the starting frequency compensates for the delay time for the establishment of a<br />

magnetic flux in the motor; specifying that for the stop frequency stabilizes the motor speed at the stop of the<br />

inverter.<br />

• Starting Frequency 1 (F23)<br />

Data setting range: 0.0 to 60.0 (Hz)<br />

F23 specifies the starting frequency at the startup of an inverter.<br />

• Starting Frequency 1 (Holding time) (F24) Data setting range: 0.00 to 10.00 (s)<br />

F24 specifies the holding time for the starting frequency 1.<br />

• Stop Frequency (F25)<br />

F25 specifies the stop frequency at the stop of the inverter.<br />

Data setting range: 0.0 to 60.0 (Hz)<br />

• Stop Frequency (Holding time) (F39) Data setting range: 0.00 to 10.00 (s)<br />

F39 specifies the holding time for the stop frequency.<br />

• Zero Speed Control (d24)<br />

To enable zero speed control under vector control with speed sensor, it is necessary to set the speed command<br />

(frequency command) at below the starting and stop frequencies. If the starting and stop frequencies are 0.0 Hz,<br />

however, the zero speed control is enabled only when the speed command is 0.00 Hz. d24 specifies the operation<br />

for the zero speed control at the startup of the inverter.<br />

Data for d24 Zero speed control Descriptions<br />

0 Not allowed at startup<br />

1 Allowed at startup<br />

Even setting the speed command at below the starting and stop<br />

frequencies and turning a run command ON does not enable the zero<br />

speed control.<br />

To enable the zero speed control, set the speed command at above the<br />

starting frequency and then start up the inverter again.<br />

Setting the speed command at below the starting and stop frequencies<br />

and turning a run command ON enables the zero speed control.<br />