(2) When function code E45 (LCD monitor item selection) is set at "1"<br />

The LCD monitor displays the output frequency, output current, and calculated torque in a bar chart.<br />

(The upper indicators show the unit of values displayed on the LED monitor as detailed in Section 3.3.2. The lower<br />

ones show the running status and run command source.)<br />

Bar chart<br />

Output frequency<br />

Output current<br />

Calculated torque<br />

The full scale (maximum value) for each parameter is as follows:<br />

Output frequency: Maximum frequency<br />

Output current: 200% of inverter’s rated current<br />

Calculated torque: 200% of rated torque generated by motor<br />

Figure 3.4 Bar Chart<br />

3.3.2 Monitoring the running status on the LED monitor<br />

The items listed below can be monitored on the 7-segment LED monitor. Immediately after the power is turned ON, the<br />

monitor item specified by function code E43 is displayed.<br />

Pressing the key in Running mode switches between monitor items in the sequence shown in Table 3.4. The "Monitor<br />

page #" column shows the monitor page of the items supported.<br />

Monitored Items on the<br />

LED Monitor<br />

Table 3.4 Items Monitored<br />

Example Unit Meaning of Displayed Value<br />

Function<br />

code E43<br />

Speed Monitor Function code E48 specifies what to be displayed. 0<br />

Output frequency 1<br />

(before slip<br />

compensation)<br />

Output frequency 2<br />

(after slip<br />

compensation)<br />

Hz Frequency actually being output (Hz) (E48 = 0)<br />

Hz Frequency actually being output (Hz) (E48 = 1)<br />

Reference frequency Hz Frequency actually being specified (Hz) (E48 = 2)<br />

<strong>Motor</strong> speed<br />

Load shaft speed<br />

Line speed<br />

r/mi<br />

n<br />

r/mi<br />

n<br />

m/mi<br />

n<br />

Display speed (%) %<br />

Output frequency (Hz) x 120<br />

P01<br />

(E48 = 3)<br />

Output frequency (Hz) x E50 (E48 = 4)<br />

Output frequency (Hz) x E50 (E48 = 5)<br />

Output frequency (Hz)<br />

Maximum frequency (Hz)<br />

x 100 (E48 = 7)<br />

Monitor page<br />

#<br />

Output current A Current output from the inverter in RMS 3 8<br />

Input power kW Input power to the inverter 9 9<br />

Calculated torque %<br />

<strong>Motor</strong> output torque in %<br />

(Calculated value)<br />

0<br />

8 10<br />

Output voltage V Voltage output from the inverter in RMS 4 11<br />

<strong>Motor</strong> output kW <strong>Motor</strong> output in kW 16 12<br />

Load factor %<br />

Load factor of the motor in % as the rated<br />

output being at 100%<br />

15 13<br />

3-5