Data for H75<br />
Target quadrants<br />
Pattern 3<br />
• If the value of torque limiter A is less than that of torque limiter B, torque limiter A<br />
applies to both the upper and lower limits.<br />
• Selecting the "Upper/lower torque limits" may cause reciprocating oscillation<br />
between the upper and lower limit values, depending upon a small difference<br />
between the upper and lower limits, a slow response from the speed control<br />
sequence, and other conditions.<br />
• Torque limiters 1-1, 1-2, 2-1 and 2-2 (F40, F41, E16 and E17)<br />
Data setting range: -300 to 300 (%), 999 (Disable)<br />
These function codes specify the operation level at which the torque limiters become activated, as the percentage<br />
of the motor rated torque.<br />
Function code<br />
Name<br />
F40 Torque limiter 1-1<br />
F41 Torque limiter 1-2<br />
E16 Torque limiter 2-1<br />
E17 Torque limiter 2-2<br />
Although the data setting range for F40, F41, E16, and E17 is from positive to negative values (–300% to<br />
+300%), specify positive values in practice except when the "Upper/lower torque limits" (H75 = 2) is<br />
selected. Specifying a negative value causes the inverter to interpret it as an absolute value.<br />
The torque limiter determined depending on the overload current actually limits the torque current output.<br />
Therefore, the torque current output is automatically limited at a value lower than 300%, the maximum<br />
setting value.<br />
• Analog torque limit values (E61 to E63)<br />
The torque limit values can be specified by analog inputs through terminals [12], [C1], and [V2] (voltage or current).<br />
Set E61, E62, and E63 (Terminal [12] Extended Function, Terminal [C1] Extended Function, and Terminal [V2]<br />
Extended Function) as listed below.<br />
Data for E61, E62, or E63 Function Description<br />
7 Analog torque limit value A Use the analog input as the torque limit value<br />
specified by function code data (= 7 or 8).<br />
8 Analog torque limit value B Input specifications: 200% / 10 V or 20 mA<br />
If the same setting is made for different terminals, the priority order is E61>E62>E63.<br />
• Torque limiter levels specified via communications link (S10, S11)<br />
The torque limiter levels can be changed via the communications link. Function codes S10 and S11 exclusively<br />
reserved for the communications link respond to function codes F40 and F41.<br />
• Switching torque limiters<br />
The torque limiters can be switched by the function code setting and the terminal command TL2/TL1 ("Select<br />
torque limiter level 2/1") assigned to any of the digital input terminals.<br />
To assign the TL2/TL1 as the terminal function, set any of E01 through E07 to "14." If no TL2/TL1 is assigned,<br />
torque limiter levels 1-1 and 1-2 (F40 and F41) take effect by default.<br />