Data for H75<br />

Target quadrants<br />

Pattern 3<br />

• If the value of torque limiter A is less than that of torque limiter B, torque limiter A<br />

applies to both the upper and lower limits.<br />

• Selecting the "Upper/lower torque limits" may cause reciprocating oscillation<br />

between the upper and lower limit values, depending upon a small difference<br />

between the upper and lower limits, a slow response from the speed control<br />

sequence, and other conditions.<br />

• Torque limiters 1-1, 1-2, 2-1 and 2-2 (F40, F41, E16 and E17)<br />

Data setting range: -300 to 300 (%), 999 (Disable)<br />

These function codes specify the operation level at which the torque limiters become activated, as the percentage<br />

of the motor rated torque.<br />

Function code<br />

Name<br />

F40 Torque limiter 1-1<br />

F41 Torque limiter 1-2<br />

E16 Torque limiter 2-1<br />

E17 Torque limiter 2-2<br />

Although the data setting range for F40, F41, E16, and E17 is from positive to negative values (–300% to<br />

+300%), specify positive values in practice except when the "Upper/lower torque limits" (H75 = 2) is<br />

selected. Specifying a negative value causes the inverter to interpret it as an absolute value.<br />

The torque limiter determined depending on the overload current actually limits the torque current output.<br />

Therefore, the torque current output is automatically limited at a value lower than 300%, the maximum<br />

setting value.<br />

• Analog torque limit values (E61 to E63)<br />

The torque limit values can be specified by analog inputs through terminals [12], [C1], and [V2] (voltage or current).<br />

Set E61, E62, and E63 (Terminal [12] Extended Function, Terminal [C1] Extended Function, and Terminal [V2]<br />

Extended Function) as listed below.<br />

Data for E61, E62, or E63 Function Description<br />

7 Analog torque limit value A Use the analog input as the torque limit value<br />

specified by function code data (= 7 or 8).<br />

8 Analog torque limit value B Input specifications: 200% / 10 V or 20 mA<br />

If the same setting is made for different terminals, the priority order is E61>E62>E63.<br />

• Torque limiter levels specified via communications link (S10, S11)<br />

The torque limiter levels can be changed via the communications link. Function codes S10 and S11 exclusively<br />

reserved for the communications link respond to function codes F40 and F41.<br />

• Switching torque limiters<br />

The torque limiters can be switched by the function code setting and the terminal command TL2/TL1 ("Select<br />

torque limiter level 2/1") assigned to any of the digital input terminals.<br />

To assign the TL2/TL1 as the terminal function, set any of E01 through E07 to "14." If no TL2/TL1 is assigned,<br />

torque limiter levels 1-1 and 1-2 (F40 and F41) take effect by default.<br />

4-63