[ 8 ] The motor abnormally heats up.<br />

Possible Causes<br />

(1) Excessive torque boost<br />

specified.<br />

(2) Continuous running in<br />

extremely slow speed.<br />

What to Check and Suggested Measures<br />

Check whether decreasing the torque boost (F09*) decreases the output<br />

current but does not stall the motor.<br />

If no stall occurs, decrease the torque boost (F09*).<br />

Check the running speed of the inverter.<br />

Change the speed setting or replace the motor with a motor exclusively<br />

designed for inverters.<br />

(3) Overload. Measure the inverter output current.<br />

Reduce the load (For fans or pumps, decrease the frequency limiter value<br />

(F15).) (In winter, the load tends to increase.)<br />

[ 9 ] The motor does not run as expected.<br />

Possible Causes<br />

(1) Incorrect setting of function<br />

code data.<br />

What to Check and Suggested Measures<br />

Check that function codes are correctly configured and no unnecessary<br />

configuration has been done.<br />

Configure all the function codes correctly.<br />

Make a note of function code data currently configured and then initialize all<br />

function code data using H03.<br />

After the above process, reconfigure function codes one by one, checking<br />

the running status of the motor.<br />

(2) Running on single-phase power Refer to Section 10.7 "If the Inverter is Running on Single-Phase Power,"<br />

[ 3 ].<br />