Related function codes<br />

Function<br />

code<br />

Name<br />

V/f control<br />

Vector<br />

control<br />

F40 Torque Limiter 1-1 Y Y<br />

F41 Torque Limiter 1-2 Y Y<br />

E16 Torque Limiter 2-1 Y Y<br />

E17 Torque Limiter 2-2 Y Y<br />

H73<br />

Torque Limiter (Operating<br />

conditions)<br />

Y<br />

Y<br />

H74 Torque Limiter (Control target) N Y<br />

H75 Torque Limiter (Target quadrants) N Y<br />

H76<br />

Torque Limiter<br />

(Frequency increment limit for<br />

Y<br />

N<br />

braking)<br />

E61 to E63<br />

Terminal [12] Extended Function<br />

Terminal [C1] Extended Function<br />

Terminal [V2] Extended Function<br />

Y<br />

Y<br />

Remarks<br />

7: Analog torque limit value A<br />

8: Analog torque limit value B<br />

• Torque limit control mode<br />

Torque limit is performed by limiting torque current flowing across<br />

the motor.<br />

The graph below shows the relationship between the torque and the<br />

output frequency at the constant torque current limit.<br />

• Torque limiters 1-1, 1-2, 2-1 and 2-2 (F40, F41, E16 and E17)<br />

Data setting range: -300 to 300 (%), 999 (Disable)<br />

These function codes specify the operation level at which the torque<br />

limiters become activated, as the percentage of the motor rated torque.<br />

Function code Name Torque limit feature<br />

F40 Torque limiter 1-1 Driving torque current limiter 1<br />

F41 Torque limiter 1-2 Braking torque current limiter 1<br />

E16 Torque limiter 2-1 Driving torque current limiter 2<br />

E17 Torque limiter 2-2 Braking torque current limiter 2<br />

Although the data setting range for F40, F41, E16, and E17 is from positive to negative values (–300% to<br />

+300%), specify positive values in practice. Specifying a negative value causes the inverter to interpret it<br />

as an absolute value.<br />

The torque limiter determined depending on the overload current actually limits the torque current output.<br />

Therefore, the torque current output is automatically limited at a value lower than 300%, the maximum<br />

setting value.<br />

• Analog torque limit values (E61 to E63)<br />

The torque limit values can be specified by analog inputs through terminals [12], [C1], and [V2] (voltage or current).<br />

Set E61, E62, and E63 (Terminal [12] Extended Function, Terminal [C1] Extended Function, and Terminal [V2]<br />

Extended Function) as listed below.<br />

Data for E61, E62, or E63 Function Description<br />

7 Analog torque limit value A Use the analog input as the torque limit value<br />

specified by function code data (= 7 or 8).<br />

8 Analog torque limit value B Input specifications: 200% / 10 V or 20 mA<br />

If the same setting is made for different terminals, the priority order is E61>E62>E63.<br />

4-59