Example of Operation Time Scheme<br />

Alternatively, set the integrated sequence by which some of the actions above are automatically<br />

performed by the inverter itself. For details, refer to the description of ISW50 and ISW60.<br />

• UP Increase output frequency) and DOWN (Decrease output frequency) commands -- UP and DOWN<br />

(Function code data = 17 and 18)<br />

• Frequency setting<br />

Turning the terminal command UP or DOWN ON causes the output frequency to increase or decrease,<br />

respectively, within the range from 0 Hz to the maximum frequency. Refer to F01 (data = 7).<br />

• PID command<br />

Turning the terminal command UP or DOWN ON causes the PID command value to increase or decrease,<br />

respectively, within the range from 0 to 100%. Refer to J02 (data = 3).<br />

• Enable data change with keypad PID control -- WE-KP (Function code data = 19)<br />

Turning the terminal command WE-KP OFF protects function code data from accidentally getting changed by<br />

pressing the keys on the keypad. Only when this terminal command is ON, you can change function code data<br />

from the keypad. Refer to F00.<br />