F02<br />
Operation Method<br />
F02 selects the source that specifies a run command.<br />
Data for F02 Run Command Description<br />
0<br />
1<br />
2<br />
3<br />
Keypad Enables the , , and keys to run the motor in the<br />
forward and reverse directions, and stop the motor.<br />
Terminal command FWD or REV Enables input terminal commands FWD and REV to run the<br />
motor in the forward and reverse directions, and stop the<br />
motor.<br />
Keypad<br />
(Forward rotation)<br />
Keypad<br />
(Reverse rotation)<br />
Enables the and keys to run the motor in the<br />
forward direction and stop it. Running the motor in the<br />
reverse direction is not possible.<br />
Enables the and keys to run the motor in the<br />
reverse direction and stop it. Running the motor in the<br />
forward direction is not possible.<br />
• When F02 = 1, the "Run forward" FWD and "Run reverse" REV terminal commands must be assigned<br />
to terminals [FWD] and [REV], respectively.<br />
• When the FWD or REV is ON, the F02 data cannot be changed.<br />
• When changing terminal command assignments to terminals [FWD] and [REV] from other configured<br />
commands (see E98, E99) to the FWD or REV with F02 being set to "1," be sure to deactivate the input<br />
terminal signals OFF beforehand; otherwise, the motor may unintentionally rotate.<br />
• 3-wire operation with external input signals (digital input terminal commands)<br />
The default setting of the FWD and REV are 2-wire. Assigning the terminal command HLD self-holds the forward<br />
FWD or reverse REV run command, to enable 3-wire inverter operation. Short-circuiting the HLD-assigned<br />
terminal and [CM] (i.e., when HLD is ON) self-holds the first FWD or REV at its rising edge. Turning the HLD OFF<br />
releases the self-holding. When no HLD is assigned, 2-wire operation involving only FWD and REV takes effect.<br />
The HLD input at terminals E01 to E07 is typically a normally closed, momentary stop contact.<br />
In addition to the run command sources described above, higher priority command sources including remote and<br />
local mode (see Section 7.3.6 of the user manual) and communications link are provided. For details, refer to the<br />
block diagrams in Chapter 6 in <strong>EQ7</strong> User's <strong>Manual</strong>.<br />