F02<br />

Operation Method<br />

F02 selects the source that specifies a run command.<br />

Data for F02 Run Command Description<br />

0<br />

1<br />

2<br />

3<br />

Keypad Enables the , , and keys to run the motor in the<br />

forward and reverse directions, and stop the motor.<br />

Terminal command FWD or REV Enables input terminal commands FWD and REV to run the<br />

motor in the forward and reverse directions, and stop the<br />

motor.<br />

Keypad<br />

(Forward rotation)<br />

Keypad<br />

(Reverse rotation)<br />

Enables the and keys to run the motor in the<br />

forward direction and stop it. Running the motor in the<br />

reverse direction is not possible.<br />

Enables the and keys to run the motor in the<br />

reverse direction and stop it. Running the motor in the<br />

forward direction is not possible.<br />

• When F02 = 1, the "Run forward" FWD and "Run reverse" REV terminal commands must be assigned<br />

to terminals [FWD] and [REV], respectively.<br />

• When the FWD or REV is ON, the F02 data cannot be changed.<br />

• When changing terminal command assignments to terminals [FWD] and [REV] from other configured<br />

commands (see E98, E99) to the FWD or REV with F02 being set to "1," be sure to deactivate the input<br />

terminal signals OFF beforehand; otherwise, the motor may unintentionally rotate.<br />

• 3-wire operation with external input signals (digital input terminal commands)<br />

The default setting of the FWD and REV are 2-wire. Assigning the terminal command HLD self-holds the forward<br />

FWD or reverse REV run command, to enable 3-wire inverter operation. Short-circuiting the HLD-assigned<br />

terminal and [CM] (i.e., when HLD is ON) self-holds the first FWD or REV at its rising edge. Turning the HLD OFF<br />

releases the self-holding. When no HLD is assigned, 2-wire operation involving only FWD and REV takes effect.<br />

The HLD input at terminals E01 to E07 is typically a normally closed, momentary stop contact.<br />

In addition to the run command sources described above, higher priority command sources including remote and<br />

local mode (see Section 7.3.6 of the user manual) and communications link are provided. For details, refer to the<br />

block diagrams in Chapter 6 in <strong>EQ7</strong> User's <strong>Manual</strong>.<br />

4-34