• When the motor speed decreases significantly during coast-to-stop (with the current limiter activated):<br />

• Secure more than 0.1 second after turning ON the "Switch to commercial power" signal before turning<br />

ON a run command.<br />

• Secure more than 0.2 second of an overlapping period with both the "Switch to commercial power"<br />

signal and run command being ON.<br />

• If an alarm has been issued or BX has been ON when the motor drive source is switched from the<br />

commercial power to the inverter, the inverter will not be started at the commercial power frequency<br />

and will remain OFF. After the alarm has been reset or BX turned OFF, operation at the frequency of<br />

the commercial power will not be continued, and the inverter will be started at the ordinary starting<br />

frequency.<br />

To switch the motor drive source from the commercial line to the inverter, be sure to turn BX OFF<br />

before the "Switch to commercial power" signal is turned OFF.<br />

• When switching the motor drive source from the inverter to commercial power, adjust the inverter's<br />

reference frequency at or slightly higher than that of the commercial power frequency beforehand,<br />

taking into consideration the motor speed down during the coast-to-stop period produced by switching.<br />

• Note that when the motor drive source is switched from the inverter to the commercial power, a high<br />

inrush current will be generated, because the phases of the commercial power usually do not match the<br />

motor speed at the switching. Make sure that the power supply and all the peripheral equipment are<br />

capable of withstanding this inrush current.<br />

• If "Restart after momentary power failure" (F14 = 3, 4, or 5), is activated keep BX ON during<br />

commercial power driven operation to prevent the inverter from restarting after a momentary power<br />

failure.<br />

4-75