8.4 Load Selection / Auto Torque Boost / Auto Energy Saving Operation (F27, Default 1)<br />

This parameter sets the load type and auto torque boost setting, including auto energy savings.<br />

F37 Load Selection / Auto Torque Boost / Auto Energy Saving Operation 1<br />

F37 specifies V/f pattern, torque boost type, and auto energy saving operation in accordance with the characteristics<br />

of the load.<br />

Specify the torque boost level with F09 in order to assure sufficient starting torque.<br />

To set parameter F37:<br />

- Press PRG key, next select QUICK SET or DATA SET with UP/DOWN and keys and press the<br />

FUNC/DATA key.<br />

- In the parameter list move cursor to F37 with UP/DOWN keys and press FUNC/DATA key to select.<br />

Data for<br />

F37<br />

0<br />

V/f pattern<br />

Variable torque<br />

V/f pattern<br />

Torque boost<br />

Torque boost<br />

specified by F09<br />

1<br />

2<br />

Linear<br />

V/f pattern Auto torque boost<br />

3<br />

Variable torque<br />

V/f pattern<br />

Torque boost<br />

specified by F09<br />

4<br />

5<br />

Linear<br />

V/f pattern Auto torque boost<br />

Auto energy<br />

saving<br />

Disable<br />

Enable<br />

Applicable load<br />

Variable torque load<br />

(General-purpose fans and pumps)<br />

Constant torque load<br />

Constant torque load<br />

(To be selected if a motor may be<br />

over-excited at no load.)<br />

Variable torque load<br />

(General-purpose fans and pumps)<br />

Constant torque load<br />

Constant torque load<br />

(To be selected if a motor may be<br />

over-excited at no load.)<br />

If a required "load torque + acceleration toque" is more than 50% of the constant torque, it is<br />

recommended to select the linear V/f pattern (factory default).<br />

• Under the vector control with speed sensor, F37 is used to specify whether the auto energy saving<br />

operation is enabled or disabled. (V/f pattern and torque boost are disabled.)<br />

Data for F37<br />

Operation<br />

0 to 2 Auto energy saving operation OFF<br />

3 to 5 Auto energy saving operation ON<br />

• Under the vector control without speed sensor, both F37 and F09 are disabled. The auto energy saving<br />

operation is also disabled.<br />

• V/f characteristics<br />

The <strong>EQ7</strong> series of inverters offers a variety of V/f patterns and torque boosts, which include V/f patterns suitable for<br />

variable torque load such as general fans and pumps and for constant torque load (including special pumps requiring<br />

high starting torque). Two types of torque boosts are available: manual and automatic.<br />

(F09)<br />

(F09)<br />

Variable torque V/f pattern (F37 = 0) Linear V/f pattern (F37 = 1)<br />

8-4