E78, E79<br />

E80, E81<br />

Torque Detection 1 (Level and Timer)<br />

Torque Detection 2/Low Torque Detection (Level and Timer)<br />

E78 specifies the operation level and E79 specifies the timer, for the output signal TD1. E80 specifies the<br />

operation level and E81 specifies the timer, for the output signal TD2 or U-TL.<br />

Output signal Assigned data<br />

Operation level<br />

Timer<br />

Range: 0 to 300% Range: 0.01 to 600.00 s<br />

TD1 46 E78 E79<br />

TD2 47 E80 E81<br />

U-TL 45 E80 E81<br />

• Torque detected 1 -- TD1, Torque detected 2 -- TD2<br />

The output signal TD1 or TD2 comes ON when the torque value calculated by the inverter or torque command<br />

exceeds the level specified by E78 or E80 (Torque detection (Level)) for the period specified by E79 or E81<br />

(Torque detection (Timer)), respectively. The signal turns OFF when the calculated torque drops below "the level<br />

specified by E78 or E80 minus 5% of the motor rated torque." The minimum ON-duration is 100 ms.<br />

• Low output torque detected--U-TL<br />

This output signal comes ON when the torque value calculated by the inverter or torque command drops below<br />

the level specified by E80 (Low torque detection (Level)) for the period specified by E81 (Low torque detection<br />

(Timer)). The signal turns OFF when the calculated torque exceeds the "level specified by E80 plus 5% of the<br />

motor rated torque." The minimum ON-duration is 100 ms.<br />

In the inverter’s low frequency operation, as a substantial error in torque calculation occurs, no low torque can be<br />

detected within the operation range at less than 20% of the base frequency (F04). (In this case, the result of<br />

recognition before entering this operation range is retained.)<br />

The U-TL signal goes off when the inverter is stopped.<br />

Since the motor parameters are used in the calculation of torque, it is recommended that auto-tuning be applied<br />

by function code P04 to achieve higher accuracy.<br />

E98, E99 Terminal [FWD] Function<br />

Terminal [REV] Function<br />

(Refer to E01 to E07.)<br />