• Display coefficients for PID dancer position command and its feedback (J01 = 3)<br />

Under PID dancer control, the PID command and its feedback operate within the range 100%, so specify the<br />

value at +100% of the PID dancer position command or its feedback as coefficient A with E40, and the value at<br />

-100% as coefficient B with E41.<br />

If the sensor output is unipolar, the PID dancer control operates within the range from 0 to +100%, so virtually<br />

specify the value at -100% as coefficient B.<br />

That is, suppose "b" = "Display value at 0%," then:<br />

Display coefficient B = 2b - A<br />

For details about the PID control, refer to the description of J01 and later.<br />

For the display method of the PID command and its feedback, refer to the description of E43.<br />

• Display coefficient for analog input monitor<br />

By inputting analog signals from various sensors such as temperature sensors in air conditioners to the inverter,<br />

you can monitor the state of peripheral devices via the communications link. By using an appropriate display<br />

coefficient, you can also have various values converted into physical values such as temperature and pressure<br />

before they are displayed.<br />

To set up the analog input monitor, use function codes E61 through E63. Use E43 to choose the item to be<br />

displayed.<br />

E42<br />

LED Display Filter<br />

E42 specifies a filter time constant to be applied for displaying the monitored running status except the speed<br />

monitor (E43 = 0) on the LED monitor on the keypad. If the display fluctuates and is hard to read due to load<br />

fluctuation or other causes, increase this filter time constant.<br />

- Data setting range: 0.0 to 5.0 (s)<br />