22.11.2014 Views

EQ7 Series Instruction Manual - TECO-Westinghouse Motor Company

EQ7 Series Instruction Manual - TECO-Westinghouse Motor Company

EQ7 Series Instruction Manual - TECO-Westinghouse Motor Company

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Even if selecting "Trip after decelerate-to-stop" or "Continue to run," the inverter may not be able to do so<br />

when the load's inertia is small or the load is heavy, due to undervoltage caused by a control delay. In<br />

such a case, when "Trip after decelerate-to-stop" is selected, the inverter allows the motor to coast to a<br />

stop; when "Continue to run" is selected, the inverter saves the output frequency being applied when the<br />

undervoltage alarm occurred and restarts at the saved frequency after a recovery from the momentary<br />

power failure.<br />

When the input power voltage for the inverter is high, setting the continuous running level high makes the<br />

control more stable even if the load's inertia is relatively small. Raising the continuous running level too<br />

high, however, might cause the continuous running control activated even during normal operation.<br />

When the input power voltage for the inverter is extremely low, continuous running control might be<br />

activated even during normal operation, at the beginning of acceleration or at an abrupt change in load.<br />

To avoid this, lower the continuous running level. However, possible undervoltage results from voltage<br />

drop due to a control delay if set too low.<br />

Changing the continuous running level, make sure that the continuous running control will be performed<br />

properly, by considering the fluctuations of the load and the input voltage.<br />

F15, F16 Frequency Limiter (High), Frequency Limiter (Low) H63 Low Limiter (Mode selection)<br />

• Frequency Limiter (High and Low) (F15, F16) Data setting range: 0.0 to 500.0 (Hz)<br />

F15 and F16 specify the upper and lower limits of the output frequency or reference frequency, respectively. The<br />

frequency to which the limit is applied differs depending on the control system, as seen in the table.<br />

Frequency Limiter<br />

V/f control<br />

Frequency to which the limit is applied<br />

Vector control without/with speed sensor<br />

Frequency Limiter (High) F15 Output frequency Reference speed (reference frequency)<br />

Frequency Limiter (Low) F16 Reference frequency Reference speed (reference frequency)<br />

When the limit is applied to the reference frequency or reference speed, delayed responses of<br />

control may cause an overshoot or undershoot, and the frequency may temporarily go beyond the<br />

limit level.<br />

• Low Limiter (Mode selection) (H63)<br />

H63 specifies the operation to be carried out when the reference frequency drops below the low level specified by<br />

F16, as follows:<br />

Data for H63<br />

Operation<br />

0 The output frequency will be held at the low level specified by F16.<br />

1 The inverter decelerates to stop the motor.<br />

(H63 = 0) (H63 = 1)<br />

• When changing the frequency limiter (High) (F15) in order to raise the reference frequency, be sure to<br />

change the maximum frequency (F03) accordingly.<br />

• Maintain the following relationship among the data for frequency control:<br />

F15 > F16, F15 > F23, and F15 > F25<br />

F03 > F16<br />

where, F23 and F25 specify the starting and stop frequencies, respectively.<br />

If any erroneous data for these function codes is entered, the inverter may not run the motor at the<br />

desired speed, nor start it normally.<br />

4-49

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!