E34, E35 Overload Early Warning/Current Detection (Level and Timer)<br />
E37, F38 (Current Detection 2/Low Current Detection (Level and Timer))<br />
E55, E56 (Current Detection 3 (Level and Timer))<br />
These function codes define the detection level and time for the "<strong>Motor</strong> overload early warning" OL, "Current<br />
detected" ID, "Current detected 2" ID2, "Current detected 3" ID3, and "Low current detected" IDL output signals.<br />
Output<br />
signal<br />
Data assigned<br />
to output<br />
terminal<br />
Operation level<br />
Range<br />
Timer<br />
Range: 0.01 to<br />
600.00 s<br />
<strong>Motor</strong><br />
characteristics<br />
Range<br />
Thermal time<br />
constant<br />
Range: 0.5 to 75.0<br />
min<br />
OL 7 E34 - F10 F12<br />
ID 37 E34 E35<br />
ID2 38 E37 E38<br />
ID3 39 E55 E56<br />
- -<br />
IDL 41 E37 E38<br />
- Data setting range<br />
Operation level: 0.00 (Disable), 1 to 200% of inverter rated current<br />
<strong>Motor</strong> characteristics 1: Enable (For a general-purpose motor with shaft-driven cooling fan)<br />
2: Enable (For an inverter-driven motor, non-ventilated motor, or motor with<br />
separately powered cooling fan)<br />
• <strong>Motor</strong> overload early warning signal -- OL<br />
The OL signal is used to detect a symptom of an overload condition (alarm code 0l1 ) of the motor so that the user<br />
can take an appropriate action before the alarm actually happens.<br />
The OL signal turns ON when the inverter output current exceeds the level specified by E34. In typical cases, set<br />
E34 data to 80 to 90% against F11 data (Electronic thermal overload protection for motor 1, Overload detection<br />
level). Specify also the thermal characteristics of the motor with F10 (Select motor characteristics) and F12<br />
(Thermal time constant).<br />
• Current detected, Current detected 2 and Current detected 3 -- ID, ID2 and ID3<br />
When the inverter output current exceeds the level specified by E34, E37 or E55 for the period specified by E35,<br />
E38 or E56, the ID, ID2 or ID3 signal turns ON, respectively. When the output current drops below 90% of the<br />
rated operation level, the ID, ID2 or ID3 turns OFF. (The minimum ON-duration is 100 ms.)<br />
• Low current detected -- IDL<br />
This signal turns ON when the output current drops below the level specified by E37 (Low current detection, Level)<br />
for the period specified by E38 (Timer). When the output current exceeds the "Low current detection level plus 5%<br />
of the inverter rated current," it goes OFF. (The minimum ON-duration is 100 ms.)<br />
4-95