22.11.2014 Views

EQ7 Series Instruction Manual - TECO-Westinghouse Motor Company

EQ7 Series Instruction Manual - TECO-Westinghouse Motor Company

EQ7 Series Instruction Manual - TECO-Westinghouse Motor Company

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

E34, E35 Overload Early Warning/Current Detection (Level and Timer)<br />

E37, F38 (Current Detection 2/Low Current Detection (Level and Timer))<br />

E55, E56 (Current Detection 3 (Level and Timer))<br />

These function codes define the detection level and time for the "<strong>Motor</strong> overload early warning" OL, "Current<br />

detected" ID, "Current detected 2" ID2, "Current detected 3" ID3, and "Low current detected" IDL output signals.<br />

Output<br />

signal<br />

Data assigned<br />

to output<br />

terminal<br />

Operation level<br />

Range<br />

Timer<br />

Range: 0.01 to<br />

600.00 s<br />

<strong>Motor</strong><br />

characteristics<br />

Range<br />

Thermal time<br />

constant<br />

Range: 0.5 to 75.0<br />

min<br />

OL 7 E34 - F10 F12<br />

ID 37 E34 E35<br />

ID2 38 E37 E38<br />

ID3 39 E55 E56<br />

- -<br />

IDL 41 E37 E38<br />

- Data setting range<br />

Operation level: 0.00 (Disable), 1 to 200% of inverter rated current<br />

<strong>Motor</strong> characteristics 1: Enable (For a general-purpose motor with shaft-driven cooling fan)<br />

2: Enable (For an inverter-driven motor, non-ventilated motor, or motor with<br />

separately powered cooling fan)<br />

• <strong>Motor</strong> overload early warning signal -- OL<br />

The OL signal is used to detect a symptom of an overload condition (alarm code 0l1 ) of the motor so that the user<br />

can take an appropriate action before the alarm actually happens.<br />

The OL signal turns ON when the inverter output current exceeds the level specified by E34. In typical cases, set<br />

E34 data to 80 to 90% against F11 data (Electronic thermal overload protection for motor 1, Overload detection<br />

level). Specify also the thermal characteristics of the motor with F10 (Select motor characteristics) and F12<br />

(Thermal time constant).<br />

• Current detected, Current detected 2 and Current detected 3 -- ID, ID2 and ID3<br />

When the inverter output current exceeds the level specified by E34, E37 or E55 for the period specified by E35,<br />

E38 or E56, the ID, ID2 or ID3 signal turns ON, respectively. When the output current drops below 90% of the<br />

rated operation level, the ID, ID2 or ID3 turns OFF. (The minimum ON-duration is 100 ms.)<br />

• Low current detected -- IDL<br />

This signal turns ON when the output current drops below the level specified by E37 (Low current detection, Level)<br />

for the period specified by E38 (Timer). When the output current exceeds the "Low current detection level plus 5%<br />

of the inverter rated current," it goes OFF. (The minimum ON-duration is 100 ms.)<br />

4-95

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!