• Cancel PID control -- Hz/PID (Function code data = 20)<br />

Turning this terminal command ON disables the PID control.<br />

If the PID control is disabled with this command, the inverter runs the motor with the reference frequency manually<br />

set by any of the multi-frequency, keypad, analog input, etc.<br />

Terminal command Hz/PID<br />

OFF<br />

ON<br />

Function<br />

Enable PID control<br />

Disable PID control/Enable manual frequency settings<br />

( Refer to the descriptions of J01 through J19 and J56 through J62.)<br />

• Switch normal/inverse operation -- IVS (Function code data = 21)<br />

This terminal command switches the output frequency control between normal (proportional to the input value)<br />

and inverse in analog frequency setting or under PID process control. To select the inverse operation, turn the IVS<br />

ON.<br />

The normal/inverse switching operation is useful for air-handling that require switching between cooling<br />

and heating. In cooling, the speed of the fan motor (output frequency of the inverter) is increased to lower<br />

the temperature. In heating, it is reduced to lower the temperature. This switching is realized by this IVS<br />

terminal command.<br />

• When the inverter is driven by an external analog frequency command sources (terminals [12], [C1] and<br />

[V2]):<br />

Switching normal/inverse operation can apply only to the analog frequency command sources (terminals [12], [C1]<br />

and [V2]) in frequency command 1 (F01) and does not affect frequency command 2 (C30) or UP/DOWN control.<br />

As listed below, the combination of the "Selection of normal/inverse operation for frequency command 1" (C53)<br />

and the IVS terminal command determines the final operation.<br />

Combination of C53 and IVS<br />

Data for C53 IVS Final operation<br />

0: Normal operation<br />

OFF<br />

Normal<br />

ON<br />

Inverse<br />

1: Inverse operation<br />

OFF<br />

Inverse<br />

ON<br />

Normal<br />

• When the process control is performed by the PID processor integrated in the inverter:<br />

The terminal command Hz/PID ("Cancel PID control") can switch the PID control between enabled (process is to<br />

be controlled by the PID processor) and disabled (process is to be controlled by the manual frequency setting). In<br />

either case, the combination of the "PID control" (J01) or "Selection of normal/inverse operation for frequency<br />

command 1" (C53) and the terminal command IVS determines the final operation as listed below.<br />

When the PID control is enabled:<br />

The normal/inverse operation selection for the PID processor output (reference frequency) is as follows.<br />

PID control (Mode selection) (J01) IVS Final operation<br />

1: Enable (normal operation)<br />

OFF<br />

Normal<br />

ON<br />

Inverse<br />

2: Enable (inverse operation)<br />

OFF<br />

Inverse<br />

ON<br />

Normal<br />

4-78