EQ7 Series Instruction Manual - TECO-Westinghouse Motor Company
EQ7 Series Instruction Manual - TECO-Westinghouse Motor Company
EQ7 Series Instruction Manual - TECO-Westinghouse Motor Company
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
• Cancel PID control -- Hz/PID (Function code data = 20)<br />
Turning this terminal command ON disables the PID control.<br />
If the PID control is disabled with this command, the inverter runs the motor with the reference frequency manually<br />
set by any of the multi-frequency, keypad, analog input, etc.<br />
Terminal command Hz/PID<br />
OFF<br />
ON<br />
Function<br />
Enable PID control<br />
Disable PID control/Enable manual frequency settings<br />
( Refer to the descriptions of J01 through J19 and J56 through J62.)<br />
• Switch normal/inverse operation -- IVS (Function code data = 21)<br />
This terminal command switches the output frequency control between normal (proportional to the input value)<br />
and inverse in analog frequency setting or under PID process control. To select the inverse operation, turn the IVS<br />
ON.<br />
The normal/inverse switching operation is useful for air-handling that require switching between cooling<br />
and heating. In cooling, the speed of the fan motor (output frequency of the inverter) is increased to lower<br />
the temperature. In heating, it is reduced to lower the temperature. This switching is realized by this IVS<br />
terminal command.<br />
• When the inverter is driven by an external analog frequency command sources (terminals [12], [C1] and<br />
[V2]):<br />
Switching normal/inverse operation can apply only to the analog frequency command sources (terminals [12], [C1]<br />
and [V2]) in frequency command 1 (F01) and does not affect frequency command 2 (C30) or UP/DOWN control.<br />
As listed below, the combination of the "Selection of normal/inverse operation for frequency command 1" (C53)<br />
and the IVS terminal command determines the final operation.<br />
Combination of C53 and IVS<br />
Data for C53 IVS Final operation<br />
0: Normal operation<br />
OFF<br />
Normal<br />
ON<br />
Inverse<br />
1: Inverse operation<br />
OFF<br />
Inverse<br />
ON<br />
Normal<br />
• When the process control is performed by the PID processor integrated in the inverter:<br />
The terminal command Hz/PID ("Cancel PID control") can switch the PID control between enabled (process is to<br />
be controlled by the PID processor) and disabled (process is to be controlled by the manual frequency setting). In<br />
either case, the combination of the "PID control" (J01) or "Selection of normal/inverse operation for frequency<br />
command 1" (C53) and the terminal command IVS determines the final operation as listed below.<br />
When the PID control is enabled:<br />
The normal/inverse operation selection for the PID processor output (reference frequency) is as follows.<br />
PID control (Mode selection) (J01) IVS Final operation<br />
1: Enable (normal operation)<br />
OFF<br />
Normal<br />
ON<br />
Inverse<br />
2: Enable (inverse operation)<br />
OFF<br />
Inverse<br />
ON<br />
Normal<br />
4-78