Under vector control without speed sensor<br />

Under vector control with speed sensor<br />

• Acceleration/deceleration time<br />

Acceleration/<br />

deceleration time<br />

Acceleration/<br />

deceleration time 1<br />

Acceleration/<br />

deceleration time 2<br />

Acceleration/<br />

deceleration time 3<br />

Acceleration/<br />

deceleration time 4<br />

Function code<br />

ACC<br />

time<br />

DEC<br />

time<br />

At jogging operation H54 H55<br />

At forced stop - H56<br />

Switching factor of acceleration/deceleration time<br />

( Refer to the descriptions of E01 to E07.)<br />

F07 F08<br />

RT1 RT2 The combinations of ON/OFF states of the<br />

OFF OFF<br />

two terminal commands RT2 and RT1 offer<br />

four choices of acceleration/deceleration<br />

E10<br />

E12<br />

E11<br />

E13 ON<br />

OFF<br />

OFF<br />

ON<br />

(Data = 4, 5)<br />

If no terminal command is assigned, only the<br />

acceleration/deceleration time 1 (F07/F08) is<br />

effective.<br />

time 1 to 4.<br />

E14 E15 ON ON<br />

When the terminal command JOG is ON, jogging operation<br />

is possible. (Data = 10)<br />

( Refer to the description of C20.)<br />

When the terminal command STOP is OFF, the motor<br />

decelerates to a stop in accordance with the deceleration<br />

time for forced stop (H56). After the motor stops, the inverter<br />

enters the alarm state with the alarm er6 displayed. (Data =<br />

30)<br />

4-38