Chapter 4 - System Installation<br />

DANGER: AC power installation must be performed by a<br />

skilled and instructed person - see Section 2.12 on page 32.<br />

During installation, unauthorized third parties must be<br />

prevented, through the use of fail-safe lockout measures,<br />

from turning on power.<br />

Facility Overvoltage Protection<br />

The robot must be protected from excessive overvoltages and voltage spikes. If the<br />

country of installation requires a CE-certified installation or compliance with IEC 1131-2,<br />

the following information may be helpful. IEC 1131-2 requires that the installation must<br />

ensure that Category II overvoltages (i.e., line spikes not directly due to lightning strikes)<br />

are not exceeded. Transient overvoltages at the point of connection to the power source<br />

shall be controlled not to exceed overvoltage Category II, i.e., not higher than the impulse<br />

voltage corresponding to the rated voltage for the basic insulation. The user-supplied<br />

equipment or transient suppressor shall be capable of absorbing the energy in the<br />

transient.<br />

In the industrial environment, non-periodic overvoltage peaks may appear on mains<br />

power supply lines as a result of power interruptions to high-energy equipment (such as a<br />

blown fuse on one branch in a 3-phase system). This will cause high current pulses at<br />

relatively low voltage levels. Take the necessary steps to prevent damage to the robot<br />

system (for example, by interposing a transformer). See IEC 1131-4 for additional<br />

information.<br />

AC Power Diagrams<br />

1Ø<br />

200–240 VAC<br />

20 A<br />

L<br />

N<br />

E<br />

Note: F1 is user-supplied, must be slow-blow.<br />

F1 10 A<br />

L = Line<br />

N = Neutral<br />

E = Earth Ground<br />

E<br />

N<br />

L<br />

<strong>Adept</strong> <strong>Quattro</strong><br />

<strong>s650H</strong> <strong>Robot</strong><br />

1Ø 200–240 VAC<br />

User-Supplied<br />

AC Power Cable<br />

Figure 4-4. Typical AC Power Installation with Single-Phase Supply<br />