PART 3 - EXECUTION<br />

3.1 PIPING INSTALLATION<br />

A. Install piping neatly and parallel with, or perpendicular to, lines of the structure. Install pipe hangers as specified<br />

in Section 15050 to maintain accurately aligned piping systems, adequately supported both laterally and vertically.<br />

B. Backfill and compact trenches for piping below the slab per civil specifications.<br />

C. Provide Schedule 40 steel pipe sleeve, minimum of one size larger than the protected pipe, for underground piping<br />

routed beneath structural footings. Extend sleeve 24 inches in both directions beyond the footing.<br />

D. Where practical, connect two or more vents together and extend as one vent through roof. Make vent connections<br />

to stacks by appropriate use of 45 degree wyes, long sweep quarter bends, sixth, eighth, or sixteenth bends, except<br />

that sanitary tees may be used on the vertical stacks.<br />

E. Extend vent piping 12 inches above roof line or more if required by Authority Having Jurisdiction. Coordinate<br />

installation with roofing.<br />

F. Conceal piping in chases, interior walls, furred spaces, and above ceiling.<br />

G. Identify nonpotable water systems by color markings or metal tags in accordance with ASME A13.1.<br />

H. Make piping connections to fixtures and equipment with chrome-plated seamless brass tube with cleanout plug and<br />

escutcheon.<br />

I. For items to be installed on split face CMU, grind surface of CMU to a smooth finish for tight installation. Seal<br />

with silicone sealant in accordance with Section 07900.<br />

3.2 PIPING INSULATION - INSTALLATION<br />

A. Domestic Hot and Cold Water Lines: Insulate lines above slab. Do not insulate Reverse Osmosis piping.<br />

B. Interior Air Conditioning Condensate Piping: Insulate condensate piping below roof.<br />

3.3 WATER PIPING SPECIALTIES INSTALLATION<br />

A. Install backflow preventers in each water supply to mechanical equipment and systems and to other equipment<br />

where shown and water systems that may be sources of contamination. Comply with authorities having<br />

jurisdiction.<br />

1. Locate backflow preventers in same room as connected equipment or system.<br />

2. Install drain for backflow preventers with atmospheric-vent drain connection with air-gap fitting, fixed airgap<br />

fitting, or equivalent positive pipe separation of at least two pipe diameters in drain piping and pipe to<br />

floor drain. Locate air-gap device attached to or under backflow preventer. Simple air breaks are not<br />

acceptable for this application.<br />

3. Do not install bypass piping around backflow preventers.<br />

B. Install water regulators with inlet and outlet shutoff valves. Install pressure gages on inlet and outlet.<br />

C. Install balancing valves in locations where they can easily be adjusted.<br />

D. Install temperature-actuated water mixing valves with check stops or shutoff valves on inlets and with shutoff valve<br />

on outlet.<br />

1. Install thermometers and water regulators if specified.<br />

2. Install cabinet-type units recessed in or surface mounted on wall as specified.<br />

15100-6<br />