PART 3 - EXECUTION<br />
3.1 PIPING INSTALLATION<br />
A. Install piping neatly and parallel with, or perpendicular to, lines of the structure. Install pipe hangers as specified<br />
in Section 15050 to maintain accurately aligned piping systems, adequately supported both laterally and vertically.<br />
B. Backfill and compact trenches for piping below the slab per civil specifications.<br />
C. Provide Schedule 40 steel pipe sleeve, minimum of one size larger than the protected pipe, for underground piping<br />
routed beneath structural footings. Extend sleeve 24 inches in both directions beyond the footing.<br />
D. Where practical, connect two or more vents together and extend as one vent through roof. Make vent connections<br />
to stacks by appropriate use of 45 degree wyes, long sweep quarter bends, sixth, eighth, or sixteenth bends, except<br />
that sanitary tees may be used on the vertical stacks.<br />
E. Extend vent piping 12 inches above roof line or more if required by Authority Having Jurisdiction. Coordinate<br />
installation with roofing.<br />
F. Conceal piping in chases, interior walls, furred spaces, and above ceiling.<br />
G. Identify nonpotable water systems by color markings or metal tags in accordance with ASME A13.1.<br />
H. Make piping connections to fixtures and equipment with chrome-plated seamless brass tube with cleanout plug and<br />
escutcheon.<br />
I. For items to be installed on split face CMU, grind surface of CMU to a smooth finish for tight installation. Seal<br />
with silicone sealant in accordance with Section 07900.<br />
3.2 PIPING INSULATION - INSTALLATION<br />
A. Domestic Hot and Cold Water Lines: Insulate lines above slab. Do not insulate Reverse Osmosis piping.<br />
B. Interior Air Conditioning Condensate Piping: Insulate condensate piping below roof.<br />
3.3 WATER PIPING SPECIALTIES INSTALLATION<br />
A. Install backflow preventers in each water supply to mechanical equipment and systems and to other equipment<br />
where shown and water systems that may be sources of contamination. Comply with authorities having<br />
jurisdiction.<br />
1. Locate backflow preventers in same room as connected equipment or system.<br />
2. Install drain for backflow preventers with atmospheric-vent drain connection with air-gap fitting, fixed airgap<br />
fitting, or equivalent positive pipe separation of at least two pipe diameters in drain piping and pipe to<br />
floor drain. Locate air-gap device attached to or under backflow preventer. Simple air breaks are not<br />
acceptable for this application.<br />
3. Do not install bypass piping around backflow preventers.<br />
B. Install water regulators with inlet and outlet shutoff valves. Install pressure gages on inlet and outlet.<br />
C. Install balancing valves in locations where they can easily be adjusted.<br />
D. Install temperature-actuated water mixing valves with check stops or shutoff valves on inlets and with shutoff valve<br />
on outlet.<br />
1. Install thermometers and water regulators if specified.<br />
2. Install cabinet-type units recessed in or surface mounted on wall as specified.<br />
15100-6<br />