2.6 AIR INLETS AND OUTLETS<br />

A. Grilles, registers, ceiling outlets, and ceiling inlets shall be as indicated on Drawings. Wall mounted and hard<br />

ceiling mounted air inlets and outlets shall be provided with heavy-duty sponge or soft felt gaskets.<br />

2.7 DROP BOX DIFFUSERS (OWNER FURNISHED - CONTRACTOR INSTALLED)<br />

A. Manufacturer: Wal-Mart supplier for drop box diffusers will be as follows:<br />

1. AES Industries, Tallassee, AL, Contact: Chad Burt (800) 786-0402.<br />

B. General Description: Drop boxes will be constructed of 18 gauge galvannealed/galvanized (paintable) steel sheet<br />

conforming to ASTM A 653, min. A60 coating designation, with integral 18 gauge minimum air diverters. Drop<br />

boxes shall be fully welded. Mechanical fastened seams shall not be used. Diffusers shall be fully adjustable<br />

double deflection drum louvers. Base louver in 6-way box shall be double deflection with opposed blade dampers.<br />

Provide air tight gaskets at louver connections to drop box. Drop boxes shall be insulated with 1” x 1.5 lb density<br />

duct liner glued with 100% coverage of adhesive and pin spotted to all interior surfaces per SMACNA. Provide 14<br />

gauge mounting brackets, 2”x 2”x 1/4” pre-punched angles, 3/8” all thread rod, beam clamps, and additional nuts<br />

and washers.<br />

C. Accessory Package: Manufacturer shall provide mounting accessory package for each drop box consisting of the<br />

following:<br />

1. 2" x 2" x 1/4" pre-punched angles (or Unistrut).<br />

2. 3/8" all thread rod (pre-cut).<br />

3. Beam clamps.<br />

4. All bolts, nuts and washers.<br />

D. 6-Way Drop Box Performance Criteria:<br />

Unit<br />

Size<br />

6-Way Diffuser - Louver Schedule<br />

Box<br />

Type Total CFM Drum Louver Size Base Louver Size Minimum Throw (ft)<br />

5 Ton 6-way 2000 6 x 12 <strong>No</strong>ne 33<br />

10 Ton 6-way 4000 6 x 18 <strong>No</strong>ne 47<br />

20 Ton 6-way 6000 -7000 10 x 25 6 x 18 61<br />

25 Ton 6-way 8000 - 10000 12 x 30 6 x 18 74<br />

Base louver in 6-way box shall be double deflection with opposed blade dampers. Provide air tight gaskets at<br />

louver connections to drop box.<br />

E. Finish: Prime and finish coat in the shop. Paint exposed screws and fasteners to match drop box. Finish coating<br />

shall be color to match Sherwin-Williams #SW6385 “Dover White".<br />

1. Alkyd Primer: One coat PPG Multigrip Epoxy Ester Dry Fog #6-157.<br />

2. Alkyd Finish: One coat PPG Speedhide Super-Tech Dry Fog Coating, Eggshell # 6-151.<br />

F. Identification: Paint RTU number in black 6” letters on the bottom of each drop box.<br />

2.8 DUCT SEALERS<br />

A. Manufacturer: Provide duct sealers of one of the following:<br />

1. Kingco 11376 or 10526.<br />

2. Ductmate PROseal.<br />

3. United McGill Duct-Sealer.<br />

4. Trans-Continental Equipment Co. - Multipurpose Duct Sealant.<br />

5. Hardcast #601 Iron-Grip.<br />

6. Hardcast Aluma-Grip Tape.<br />

15800-4<br />