output terminals shall not exceed the followings:Charge nominal(DC voltage)Ripple voltagelimit: 125 V: 2.0 V peak to peak10.3 DC DISTRIBUTION <strong>BOARD</strong>The Contractor shall provide the DC distribution board in the gas turbine unitcontrol package and in the auxiliary room of the control building. The Contractorshall determine the continuous current rating of the distribution boards.Number of the feeders and current rating of feeders shall be determined by theContractor. Five (5) spare feeders on each distribution board shall be provided.Ghorasal 200 MW to 300 MW Gas Turbine Peaking Power Plant Project (Vol-2 of 3)105