The rear panel shall be equipped with the following items of protection, but notbe limited to:One (1) lot Overall differential relayOne (1) lot Step-up transformer primary over-current relayOne (1) lot Step-up transformer neutral over-current relayOne necessary auxiliary relays, test terminal blocks, lockout relays, etc. shall alsobe provided.Step Up Transformer (s) protection & integration of the new 230 KV feeder (s)within existing 230 KV Busbar protection scheme is within contractor scope.8.6.3 SYNCHRONIZING PANELSwing type synchronising panel shall be equipped with the following itemsinstruments, but not be limited to:One (1) SynchroscopeTwo (2) Voltmeter (0-150 kV)Two (2) Frequency meter (45-55 Hz)8.6.4 MODIFICATION OF EXISTING CONTROL & PROTECTIONPANELS AT GHORASAL <strong>POWER</strong> STATION (n/a)8.7 DESK <strong>BOARD</strong> FOR 11 KV COMMON SWITCHGEARThe desk board for 11 KV, instruments, and other necessary things:One (1) lot Control switch for 11 kV circuit breaker for incomingOne (1) lot Control switch for spare 11 kV circuit breakerOne (1) lot 11 kV bus voltmeter selector switchOne (1) lot Incoming circuit ammeter selector switchOne (1) lot 11 kV bus voltmeter (0-11 kV)One (1) lot Incoming ammeter (0-6000 A)One (1) lot Spare breaker watt meterOne (1) lot Spare breaker Var meterOne (1) lot Spare breaker watt-hour meter with indicating lamp for voltagefailureOne (1) lot Mimic busOne (1) lot Annunciators (minimum 15 windows)One (1) lot Test terminal blocksFor starting motor control switch , one (1) ammeter with selector switch for themotor shall also be provided on this panel.8.8 DESK <strong>BOARD</strong> FOR AUXILIARY <strong>POWER</strong> SUPPLY Required no. of 6.6 kV and 415 V incoming circuit breaker control switch. Required no. of 6.6 kV and 415 V bus tie circuit breaker control switch. Required no. of 6.6 kV and 415 V feeder circuit breaker control switchGhorasal 200 MW to 300 MW Gas Turbine Peaking Power Plant Project (Vol-2 of 3)85

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!