Rating: To meet the required ofthe specification as stated in Clause 5Voltage ratio of single phase 11 230transformer at full load : / KV√3Connection [HV-LV] :Ynd 1 as shown in singleline diagram.Rated insulation level: HV winding LV windingLighting impulse Withstand : .... kV (Peak) 75 kV PeakVoltage (1.2/50 micro sec.)Power frequency withstand : .......kV 28kVVoltage (for 1 min).Impedance voltage: Shall be within the range of15% and 18%Tap changer: On load at high tensionwinding ±8 x 1.25 %.TerminationHigh tension side:Outdoor bushing for Cable Pot HeadLow tension side:11 kV Isolated & insulated phase busduct and XLPE cables.2) One (1) lot of associated equipment.2.3. Unit Auxiliary Transformer, Station Transformers and AssociatedEquipment1) One (1) set of unit auxiliary transformer and associated equipment withthe following features:TypeRatingRated high voltageRated high voltage: Oil immerse, three phase andtwo windings, outdoor power transformer.: To meet the requirement of theSpecification:11 kV: 6.6 kVConnection : Ynd 11Rated insulation level :HV WindingLV WindingGhorasal 200 MW to 300 MW Gas Turbine Peaking Power Plant Project (Vol-2 of 3)12