9. CABLING AND GROUNDING9.1 GENERAL(1) ScopeThe Contractor shall design, supply, install, terminate and commission all thecables for the plant.(2) Voltage DropThe maximum permissible voltage drop shall be such that in on case shall thedrop exceed 2.5% under normal running condition and 10% under motor starting.(3) ArmouringAll cables except 230 KV power cables, control and instrument cables shall beprovided with galvanised steel wire or steel tape armour and PVC cover sheath.9.2 CABLE TYPES9.2.1 11 kV XLPE <strong>POWER</strong> CABLE & ISOLATED PHASE SOLID BUS.(1) The cable shall be stranded annealed copper conductor.The construction of the conductor shall be the compacted circular single coretype. The size of the conductor shall be capable to carry the rated capacity ofeach feeder and at specified site conditions without exceeding its maximumtemperature i.e. 90 0 C. The minimum size of 11 KV cable shall not be less than100 sq. mm. The copper conductor shall comply with latest IEC Standard.(2) InsulationThe insulation material shall be extruded cross linked polyethylene of lowdielectric loss, high dielectric strength, low thermal resistivity and long termstability. It shall be free from contamination by oil, chemical and moisture. Theextrusion process shall ensure that the insulation is homogenous and The singlecore 11 kV XLPE Copper conductor power cable and other necessary items for thecompletion of the cable system.The power cable and accessories shall be designed and constructed in accordancewith the requirements of latest IEC Standard. High Voltage Cross linkedPolyethylene Insulated cable" and the most up-to-date experience for a system ofthis voltage level and shall incorporate the latest improvements of design andmanufacture for the type of cables and accessories required.Free from voids and impurities. The process shall be dry method. The averagethickness of insulation measured at section shall not be less than the valuespecified in the standard.(3) TerminationsThe end terminating materials shall be supplied for the termination of 11 KVcables.Ghorasal 200 MW to 300 MW Gas Turbine Peaking Power Plant Project (Vol-2 of 3)94

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!