(2) Grounding wire of the equipment to be connected with grounding grid.Annealed copper standard wire in accordance with latest IEC Annealed copperstranded wire for electrical purposes.Nominal cross sectional area:100 sq. mm.Ground grid shall be mesh type and be laid so that the completed earthing systemshall have a maximum earth resistance value of less than 0.5 ohms, at any pointon the system. The contact voltage at any point inside the power station at theincidence of an earth fault shall not exceed 50 volts. The power station groundingshall be embedded to a minimum depth of 800 cm. The grounding rods additionto the above grid shall be provided, if required. The minimum outer diameter ofgrounding rod shall not be less than 15 mm.Ghorasal 200 MW to 300 MW Gas Turbine Peaking Power Plant Project (Vol-2 of 3)99