464<br />

Square and octagonal columns are supported by individual piers and pyramid spread footings. <strong>The</strong><br />

floor system consists of RC beams in the north-south direction that support the joists and 4 in. thick<br />

one-way slabs in the east-west direction. <strong>The</strong> beam-column system in the north-south direction<br />

constitutes a poorly detailed moment frame and the lack of beams in the east-west direction implies a<br />

very weak and soft system in that direction. Based on FEMA-356 Life-Safety performance criteria<br />

(FEMA 2000) for a 10% in 50 year event, the lateral-force-resisting system of the building was found<br />

to be inadequate when the current renovation design was undertaken.<br />

Results from linear and non-linear 2-D and 3-D computer analyses of the structure conducted by<br />

Coughlin, Porter and Lundeen, Inc. led to the selection of fluid viscous dampers in conjunction with<br />

hybrid FRC-encased steel truss beams for strengthening the structure in the north-south direction,<br />

while Yielding Steel Braced Frames were selected for the east-west direction. For the addition of the<br />

hybrid beams, appropriate connection details needed to be developed in order to assure adequate<br />

transfer offerees between the new hybrid beams and the existing RC columns. In this paper, a testing<br />

program aimed at evaluating various details for connecting hybrid FRC-encased steel truss beams to<br />

the existing RC columns of the King County Courthouse building structure is described.<br />

EXPERIMENTAL PROGRAM<br />

<strong>The</strong> experimental program consisted of testing of four beam-column subassemblies under<br />

displacement reversals. Specimens 1 and 2 represented interior connections, while Specimens 3 and 4<br />

represented exterior subassemblies. Fig. I shows a sketch of the test setup used in the experimental<br />

program. <strong>The</strong> four test specimens were subjected to a displacement pattern similar to that specified in<br />

the ACI ITG/T1.1-99 document (ACI 1999) with story drifts ranging from 0.2% up to 3.5%.<br />

Additional cycles, with an amplitude of approximately 4.5% drift and 5.0% drift, were applied to<br />

Specimens 1 thru 3 and Specimen 4, respectively, after the completion of the cycles to 3.5% drift.<br />

<strong>The</strong> column and beam cross section dimensions were the same for all four specimens. <strong>The</strong> column<br />

cross section had an octagonal shape with a side length of 8.25 in. and a 20 in. square beam cross<br />

section was used for all test specimens. <strong>The</strong>se dimensions translated into an approximately 2/3 scale<br />

compared to the existing columns and the hybrid beams planned for the building. Lateral<br />

displacements were applied through a hydraulic actuator connected to the top of the column and to a<br />

strong reaction wall (Fig. 1). A small axial load was applied to the column through hydraulic jacks,<br />

amounting to an axial stress of approximately 150 psi. Three connection details were evaluated for<br />

achieving proper moment connection between the beam and column: 1) use of beam longitudinal<br />

reinforcing bars passing through and epoxy-bonded to the column, 2) use of beam longitudinal<br />

reinforcing bars combined with external steel reinforcement, 3) use of only external steel<br />

reinforcement for full moment transfer. In all cases, shear connection between the embedded steel truss<br />

and the existing column was provided to resist the full shear demand.<br />

Test Specimens<br />

Four beam-column subassemblies were designed and tested to evaluate the behavior of the three<br />

moment connections mentioned above. In the following, a brief description of beam, column and<br />

connection details used in the test specimens is given.