<strong>P12x</strong>/<strong>EN</strong> TD/<strong>Eb6</strong>Page 8/50Technical DataMiCOM P120/P121/P122/P1231.4.2 <strong>P12x</strong> earth CT consumptionearth Earth transformer 5Aearth Earth transformer 1ACurrent (A)P0865<strong>EN</strong>a1.5 Logic InputsLogic input typeLogic input burdenLogic input recognition timeIndependent optically insulated< 10 mAmps per input< 5ms1.5.1 SupplyOrderingCodeRelay auxiliary power supplyNominalvoltage rangeVxOperatingvoltage rangeA 24 - 60 Vdc 19,2 – 76 VdcF 48 – 250 Vdc 38.4 – 300 Vdc48 – 240 Vac 38.4 – 264 VacTHVW48 – 250 Vdc48 – 240 VacSpecial EA (**)48 – 250 Vdc48 – 240 Vac48 – 250 Vdc48 – 240 Vac48 – 250 Vdc48 – 240 Vac38.4 – 300 Vdc38.4 – 264 VacNominalVoltage range24 – 250 Vdc24 – 240 Vac24 – 250 Vdc24 – 240 VacMinimalpolarisationvoltage19,2 Vdc19,2 VacLogic InputsMaximumpolarisationcurrentHoldingcurrentafter 2 ms35 mA 2.3 mA19,2 Vdc19,2 Vac 35 mA 2.3 mAMaximumcontinuouswithstand300 Vdc264 Vac300 Vdc264 Vac38.4 – 300 Vdc38.4 – 264 Vac 129 Vdc 105 Vdc 3.0 mA @ 129 Vdc 145 Vdc38.4 – 300 Vdc38.4 – 264 Vac 110 Vdc 77 Vdc 7.3 mA @ 110 Vdc 132 Vdc38.4 – 300 Vdc38.4 – 264 Vac 220 Vdc 154 Vdc 3.4 mA @ 220 Vdc 262 Vdc(**) Logic input recognition time for EA approval. Dedicated filtering on 24 samples (15 msat 50 Hz)