Communications <strong>P12x</strong>/<strong>EN</strong> CT/<strong>Eb6</strong>IEC 60870-5-103 DATABASEMiCOM P120/P121/P122/P123 Page 172.6 IEC870-5-103 messages for Disturbance record extractionThe disturbance extraction procedure with IEC870-5-103 in MICOM Px2x relays is in conformance with IEC870-5-103 standard definition.The maximum disturbance record number stored in a P120/P122/P123 is 5.The disturbance record mapping for P120 is the following:−Number of analog channels transmitted: 1, which is:Channel 1: IN current (Earth).− Identifiers of tags (8) transmitted in ASDU 29 (logical informations) :− Tag number 1: IN>: FUN INF − Tag number 2: General start: FUN INF − Tag number 3: General Trip: FUN INF − Tag number 4: tIN> (Earth): FUN INF − Tag number 5: tIN>> (Earth): FUN INF − Tag number 6: tIN>>> (Earth): FUN INF with private option inactive: FUN ,INF − Tag number 7: Log input 1: FUN INF with private option inactive: FUN ,INF − Tag number 8: Log input 2: FUN INF with private option inactive: FUN ,INF