13.07.2015 Views

P12x/EN T/Eb6 - Schneider - error

P12x/EN T/Eb6 - Schneider - error

P12x/EN T/Eb6 - Schneider - error

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>P12x</strong>/<strong>EN</strong> TD/<strong>Eb6</strong>Page 32/50Technical DataMiCOM P120/P121/P122/P123An example may occur in a cable with plastic insulation. In this application it is possible thatthe fault energy melts the cable insulation, which then reseals after clearance, therebyeliminating the cause for the fault. This process repeats itself to give a succession of faultcurrent pulses, each of increasing duration with reducing intervals between the pulses, untilthe fault becomes permanent.When the reset time of the overcurrent relay is set to minimum the relay will be repeatedlyreset and will not be able to trip until the fault becomes permanent. By using the reset timerhold function the relay will integrate the fault current pulses, thereby reducing fault clearancetime.The mathematical formula applicable to the five curves is:⎛( ) ⎟ ⎟ ⎞⎜ Kt = T ×⎜α⎝1−I I S ⎠Where:tKIIsαReset timeFactor (see table)Value of the measured currentValue of the programmed threshold (pick-up value)Factor (see table)T Reset time multiplier (RTMS) setting between 0.025 and 1.5.Type of curve Standard K factor α factorShort time inverse C02 2.261 2Moderately inverse ANSI/IEEE 4.850 2Long time inverse C08 5.950 2Very inverse ANSI/IEEE 21.600 2Extremely Inverse ANSI/IEEE 29.100 2

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!