<strong>P12x</strong>/<strong>EN</strong> CM/<strong>Eb6</strong>Page 18/18Commissioning and MaintenanceMiCOM P120/P121/P122/P1235.3.2.3 A remote command is not taken in accountProblem:The communication between the relay and the PC is correct, but the relay does not acceptany remote command or file downloading.Cause:Generally this is due to the fact that the relay is in programming situation. This means thatthe password is active.Action:Check that the password is not active in the relay since the last 5 minutes.