Application Guide<strong>P12x</strong>/<strong>EN</strong> AP/<strong>Eb6</strong>MiCOM P120/P121/P122/P123 Page 63/7825. UNDERCURR<strong>EN</strong>T PROTECTION FUNCTION (P122 & P123 ONLY)MiCOM P122 & P123 relays include 2 undercurrent elements. One is dedicated for the CBfail detection (see CB failure protection section).The other one can be used to provide additional protective functions to preventdamage/further damage to the power system. This function allows typical applications suchas loss of load.I a underI< thresholdAlarmindicationI b underI< thresholdI c underI< threshold>=1&DigitalInput 52atI< 0OutputRelaysP0032<strong>EN</strong>aFIGURE 15: UNDERCURR<strong>EN</strong>T PROTECTION LOGICThe undercurrent protection function is available only if the auxiliary contact of the CB statusis connected to the relay. A logic input should be energised via the 52a contact of the CB.In this way a logic input (1 to 5 for P123, 1 to 3 for P122) is allocated to the 52a function. Seethe AUTOMAT. CTRL/ Inputs x menu.An alarm is given when:− at least one of the 3 phase current is detected under the threshold I