Application Guide<strong>P12x</strong>/<strong>EN</strong> AP/<strong>Eb6</strong>MiCOM P120/P121/P122/P123 Page 69/78Binary inputtSUP 0Trip Circ.TrippingRelay RL1energized&52 FailsignalP0037<strong>EN</strong>aFIGURE 21: TRIP CIRCUIT SUPERVISION PRINCIPLE DIAGRAMThree examples of application are given below.Example 1In this example only the 52a auxiliary contact is available, the MiCOM relay monitors the tripcoil whatever the CB status is (CB open or CB closed ).However, this configuration is not recommended because the 52a contact and associatedcircuit is not monitored.Electrical panel+26+--Circuit breaker52aP3966<strong>EN</strong>aFIGURE 22: TRIP COIL MONITORINGExample 2In this example both 52a and 52b auxiliary contacts are available; the MiCOM P122 andP123 relays monitor the complete trip circuit when the CB is closed and a part of the tripcircuit when the CB is open.In this case it is necessary to insert a resistor R1 in series with 52b, if either the output (RL1)trip is latched or it stays involuntarily closed, or a long time trip pulse is programmed (See