<strong>P12x</strong>/<strong>EN</strong> AP/<strong>Eb6</strong>Page 38/78Application GuideMiCOM P120/P121/P122/P12315. AUXILIARY TIMERS (P121, P122 & P123 ONLY)Five auxiliary timers tAux1, tAux2, tAux3 (P122/P123 only), tAux4 and tAux5 (P123 only) areavailable and associated to Aux1, Aux2, Aux3, Aux4 and Aux5 logic inputs (refer to“AUTOMAT. CRTL/INPUTS” menu). When these inputs are energised, the associated timersstart and, when the set time has elapsed, the associated output relays close (refer to“AUTOMAT. CRTL/OUTPUTS” menu). Time delays can be independently set from 0 ms to200 s.NOTE:It is possible to allocate logic inputs of the MiCOM P120 to theexternal information Aux1 and Aux2. Therefore, these inputs cannotcommand output relays. Moreover, the tAux1 and tAux2 timers arefixed and equal to 0. Thus the Aux1 and Aux2 inputs can only be usedfor indication on the communication network.