Application Guide<strong>P12x</strong>/<strong>EN</strong> AP/<strong>Eb6</strong>MiCOM P120/P121/P122/P123 Page 47/78A time delay (tBC) is necessary to ensure co-ordination with other protective devices.21.1 Example of SettingThe following information comes from a the relay commissioning report;I full load = 500AI 2 = 50AThen:I 2 /I 1 = 50/500 = 0.1To tolerate some margin and load variations, it is typical to set this value at 200% above thisvalue: Therefore, RATIO I2/I1 = 20%Set tBC at 60s to allow short circuits to be cleared by time delayed protections.