<strong>P12x</strong>/<strong>EN</strong> FT/<strong>Eb6</strong>Page 20/62INH Alarm Ctrl TripYesUser GuideMiCOM P120/P121/P122/P123Control trip function assigned to the input. The defaultvalue is Yes. The next table summarises the behaviourof control trip function when a control trip function isreceived by the relay.CaseRL1 assigned to “Ctrl Trip” No No Yes Yes“Ctrl trip” alarm inhibited No Yes No YesResult:LED trip Off Off On OffLED Alarm blinking Off blinking OffAlarm message on display Yes No Yes NoEvent “EVT_TC_TRIP_X1” generated in the event file Yes Yes Yes YesDefault recorded in the records/faul record menu No No Yes YesRL1 activated No No Yes YesINH Alarm [79] Ext BlockNoAs above for the autorecloser blocking by a logical input(external blocking) (2) .INH Alarm I