<strong>P12x</strong>/<strong>EN</strong> CT/<strong>Eb6</strong> CommunicationsCOURIER DatabasePage 70 MiCOM P120/P121/P122/P123Col Row Menu Text Data Type IndValues(*: default)Depend Cell Type Min/Max/Step04 θ TRIP Unsigned Integer (2 bytes) 100 % * 4201=1 Setting 50 / 200/ 1 %05 θ ALARM ? Binary (1 bit) 0 Disabled * / Enabled 4201=1 Setting 0/1/106 θ ALARM Unsigned Integer (2 bytes) 90 % * 4205 =1 Setting 50 / 200/ 1 %07 Thermal constant Unsigned Integer (2 bytes) 1 * 4201=1 Setting 1/ 200 / 1 mn43 00 MIN I Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/102 Threshold I2> Courier floating point number 0.1 In * 4401 = 1 Setting 0.1/40.0/0.01 In03 Temporisation type 01204 Curve Type Indexed String 01234567890: definite time *1: inverse time2: RI curveSTI (CEI) *SI (CEI)VI (CEI)EI (CEI)LTI (CEI)STI (CO2)MI (ANSI)LTI (CO8)VI (ANSI)EI (ANSI)4401 = 1 Setting 0/2/14401 = 1 Setting 0/9/105 TMS Courier floating point number 0.025 * 4403=1 Setting 0.025/1.5/0.00106 K (RI) Courier floating point number 0.1 * 4403=2 Setting 0.1/10.0/0.00507 Tempo I2> Courier floating point number 0.01 s * 4403=0 Setting 0 /150.0/1.008 Temporisation reset type Indexed String 0: definite time1: inverse time4403=1 &4404>= 5 &4404