Application Guide<strong>P12x</strong>/<strong>EN</strong> AP/<strong>Eb6</strong>MiCOM P120/P121/P122/P123 Page 13/78Operating Inrush current is settable from 10% to 35% of fundamental current.tReset timer defines the minimum duration of overcurrent threshold inhibition (0-2s, settable).This timer starts as soon as operating inrush current threshold picks up:−−If inrush condition duration is smaller than tReset setting value, selected overcurrentfunction will remain inhibited during tReset.If inrush condition duration is longer than tReset setting value, selected overcurrentfunction will be inhibited as long as inrush condition remains valid.Under inrush condition, the following selectable protection stages will be blocked: