<strong>P12x</strong>/<strong>EN</strong> FT/<strong>Eb6</strong>Page 46/62User GuideMiCOM P120/P121/P122/P123Function P120 P121 P122 P123 INFORMATION and COMM<strong>EN</strong>TSEQU E X X X Logic output of Boolean Equation E.EQU. F X X X Logic output of Boolean Equation F.EQU. G X X X Logic output of Boolean Equation G.EQU. H X X X Logic output of Boolean Equation H.AUTOMAT. CTRLOutput RelaysHeading of the Output Relays submenu.Function 87654321100010Function 6543200010Function 432010Assigning the corresponding protection function to theoutput relays; i.e. to output 3 (RL3)Setting choice: 1 assigns the output relay; 0 noassignmentRefer to previous table for protection functions list.Submenu for P122.Submenu for P120 and P121.2.9.7 Latch of the auxiliary output relays (RL2 to RL8)This submenu (not available in P120 menu) makes it possible to latch the auxiliary outputrelays, relay by relay.AUTOMAT. CTRLLatch OutputRelaysOutput 2Output 3Output 4Output 5Output 6Output 7Output 8NoYesYesYesNoYesNoHeading of the Latch Output Relays submenu.Latch the auxiliary output relay RL2.Latch the auxiliary output relay RL3.Latch the auxiliary output relay RL4.P122 and P123 onlyLatch the auxiliary output relay RL5.P122 and P123 onlyLatch the auxiliary output relay RL6.P123 onlyLatch the auxiliary output relay RL7.P123 onlyLatch the auxiliary output relay RL8.