<strong>P12x</strong>/<strong>EN</strong> AP/<strong>Eb6</strong>Page 28/78Application GuideMiCOM P120/P121/P122/P1239. REMOTE PROTECTION STAND-BY DIAGRAMMiCOM P121, P122 and P123 relays can be used as a HV distance back-up protection(Figure 9). Depending on the type of selectivity required, 51/51N function of P121, P122 andP123 needs to be set either as time constant or as time dependent. The value of the timedelay of I>/Ie> is set to a value that is compatible with thresholds Z2 or Z3 (2nd and 3rddistance protection zone).BusbarCircuit BreakerDistance protection21P 12150/51FeederP0028<strong>EN</strong>aFIGURE 9: ASSISTANCE OF REMOTE PROTECTION BY A MiCOM P121 PROTECTIONThe «Equipment default » contact of the distance protection (case of a numerical protection)can be wired to a MiCOM P121, P122 and P123 relays to optimise the time to trip.